1.6.4Optional Cabinets

Installation

1.6.4Optional Cabinets

If your NX installation includes a Maintenance Bypass Cabinet, the NX must be positioned to allow the Maintenance Bypass Cabinet to be bolted to left side of the NX (see Figure 1). Cables from the Maintenance Bypass Cabinet must be brought through the bottom side of the NX for connection.

The Maintenance Bypass Cabinet must be cabled and bolted to the NX before the UPS and bypass cabinet are moved into their final position. Connect the input wiring to the Maintenance Bypass Cab- inet ONLY after the units are connected and positioned.

Battery cabinets may be bolted to either side of the NX, unless used in configurations that include a Maintenance Bypass Cabinet. If used with a Maintenance Bypass Cabinet, battery cabinets must be installed on the right side of the UPS; see Figure 1 below.

Figure 1 Cabinet arrangement

ALL UNITS VIEWED FROM ABOVE

Maintenance

Bypass

Cabinet

Liebert

NX

Maintenance

Bypass

Cabinet

Liebert

NX

Battery

Battery

Cabinet

Cabinet

NX connected only to MBC

NX connected to Maintenance Bypass Cabinet and Battery Cabinets

(MBC must be on left side of the NX)

(MBC must be on left side of the NX)

 

(Battery Cabinets must be on the right side of the NX in this

 

configuration)

Battery

Cabinet

Liebert

NX

Battery

Cabinet

NX connected to Battery Cabinets

(Battery Cabinets may be on either side of the NX)