1.2.1Storing for Delayed Installation

Installation

1.2.1Storing for Delayed Installation

If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect the NX from excessive moisture (see 6.2 - UPS Environmental).

! CAUTION

If the UPS must remain disconnected from power for more than six (6) months, the battery must be recharged before use. To charge the batteries, the unit must be connected to utility power and started up—the charger operates only while the NX is operating.

! CAUTION

When batteries are installed in the UPS or are cabinet-mounted adjacent to the UPS unit, the battery—not the UPS—dictates the designed maximum ambient temperature.

1.3Preliminary Checks

1.3.1Identification

The equipment supplied has an identification tag on the back of the main door listing the type and size of the UPS.

1.4UPS Location

1.4.1Positioning the UPS

Choose a location for the UPS that offers:

Easy connection to inputs, outputs and auxiliary equipment

Enough space to service the UPS

Air circulation sufficient to expel heat produced by UPS

Protection against moisture and excessive humidity

Protection against dust and other particulate matter

Compliance with fire prevention regulations and practices

Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency

1.4.2Environmental Considerations

Before installing the NX, verify that the UPS room satisfies the environmental conditions stipulated in 6.2 - UPS Environmental, paying particular attention to the ambient temperature and air exchange system.

The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).

For optimal UPS and battery system performance and service life, maintain the operating tempera- ture within the range of 74-80°F, (23-27°C).

The NX UPS cooled by internal fans. Cooling air enters the unit through the front of the unit and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit must be a minimum of 24 in. (610mm).

See Table 9 for details on heat dissipation.

Battery Location

Temperature is a major factor in determining battery life and capacity. Battery manufacturers recom- mend an operating temperature of 77°F (25°C). Ambient temperatures warmer than this reduce bat- tery life; temperatures below this reduces battery capacity. In a typical installation, battery temperature should be maintained between 74°F and 80°F (23-27°C). Batteries should be placed where there are no main heat sources or air inlets to prevent portions of batteries from being either much warmer or much cooler than other parts of the batteries.

5