Emerson 10-30kVA, 208V installation manual Specifications and Technical Data

Models: 10-30kVA 208V

1 80
Download 80 pages 38.9 Kb
Page 72
Image 72
Manual background

Specifications and Technical Data

Table 31 Multi-module bypass cabinet electrical data (continued)

 

 

 

System

System

System

 

 

 

System

 

 

I/P Voltage

Max Input

Input OCP

O/P Voltage

Nominal O/P

Output OCP

Size

Type

kVA

(VAC)

Current

CB Size (A)

(VAC)

Current Rating (A)

CB Size (A)

 

 

30

208

104

125

208

250

400

 

J00, KR0

20

208

70

90

208

167

225

 

15

208

53

70

208

125

200

 

 

 

 

10

208

35

45

208

83

125

 

 

10

208

110

150

208

83

125

3+1

 

10

220

104

150

208

83

125

 

 

10

480

47

60

208

83

125

 

 

10

600

38

50

208

83

125

 

 

15

208

164

225

208

125

200

 

 

15

220

155

200

208

125

200

 

 

15

480

71

90

208

125

200

 

LR1

15

600

57

80

208

125

200

 

20

208

219

300

208

167

225

 

 

 

 

20

220

207

300

208

167

225

 

 

20

480

95

125

208

167

225

 

 

20

600

76

100

208

167

225

 

 

30

208

329

500

208

250

400

 

 

30

220

311

400

208

250

400

 

 

30

480

142

200

208

250

400

 

 

30

600

114

150

208

250

400

 

 

10

220

102

150

208

83

125

 

 

10

480

47

60

208

83

125

 

 

10

600

38

50

208

83

125

 

 

15

220

154

200

208

125

200

 

 

15

480

70

90

208

125

200

 

MR1

15

600

56

80

208

125

200

 

20

220

205

300

208

167

225

 

 

 

 

20

480

94

125

208

167

225

 

 

20

600

75

100

208

167

225

 

 

30

220

307

400

208

250

400

 

 

30

480

141

200

208

250

400

 

 

30

600

113

150

208

250

400

 

 

30

208

315

400

208

250

400

 

UR0, Y00

20

208

210

300

208

167

225

 

15

208

158

200

208

125

200

 

 

 

 

10

208

105

150

208

83

125

66

Page 72
Image 72