UPS Specifications
6.0UPS SPECIFICATIONS
These specifications describe requirements for the Liebert NX UPS.
6.1Conformity and Standards
The UPS has been designed to conform to the following standards:
•
•ASME
•CSA 22.2, No. 107.1
•FCC Part 15, Class A
•ISO 9001
•National Electrical Code
•NEMA
•OSHA
•UL Standard 1778
The UPS system has UL and
6.2UPS Environmental
The UPS is designed to operate under the following environmental conditions without damage or deg- radation in electrical operating characteristics:
Table 8 | Environmental characteristics |
|
|
|
|
| Rated Power | |
|
| |
Operating Temperature, UPS | 32°F to 104°F (0°C to 40°C) | |
|
| |
Optimal Operating Temperature, Battery | 68°F to 86°F (20°C to 30°C) | |
|
| |
Relative Humidity | 0 to 95%, | |
|
| |
Acoustical Noise, dBA at 39 in. (1m) | 54 | |
|
| |
Altitude of Operation | ≤1000m per IEC 62040/3 | |
|
| |
|
| |
|
|
|
6.3UPS Mechanical Characteristics
Table 9 | Mechanical characteristics |
|
|
|
|
|
|
|
|
|
|
| Parameter | 10kVA | 15kVA | 20kVA | 30kVA |
|
|
|
|
| |
Width, in. (mm) |
| 24 (600) |
| ||
|
|
|
| ||
Depth, in. (mm) |
| 32.5 (825) |
| ||
|
|
|
| ||
Height, in. (mm) |
| 63 (1600) |
| ||
|
|
|
|
| |
Weight Without Inner Batteries, lb. (kg) | 450 (205) | 450 (205) | 550 (250) | 550 (250) | |
|
|
|
|
|
|
| 954 (433) | 954 (433) | 1054 (478) | 1054 (478) | |
|
|
|
|
|
|
| 1098 (498) | 1098 (498) | 1198 (543) | 1198 (543) | |
|
|
|
|
| |
Heat Dissipation, BTU/H (kWH) | 2800 (0.82) | 4200 (1.23) | 5500 (1.61) | 8300 (2.43) | |
|
|
|
|
| |
Airflow, CFM (m3/h) | 384 (652) | 558 (948) | 522 (886) | 834 (1417) | |
Cable Entry |
|
| Bottom or top |
| |
|
|
|
|
| |
Color |
|
| PMS 877 |
| |
|
|
|
| ||
Protection Grade (with open/closed front doors) |
| IP 20 |
| ||
|
|
|
|
|
|
38