Emerson 208V, 10-30kVA 2.1.4Cable Connections, Input busbars, Battery fuses and connections

Models: 10-30kVA 208V

1 80
Download 80 pages 38.9 Kb
Page 17
Image 17
2.1.4Cable Connections

Electrical Connections

2.1.4Cable Connections

The rectifier input, bypass and output are easily accessible from the left side of the unit for installa- tion. All require lug type terminations. They are connected to busbars on the left side of the NX and below the switch, as shown in Figure 3. These busbars are accessible when the left side panel is removed. Busbars to connect external batteries are accessible from the front of the UPS.

NOTE

External battery connection access requires removal of a protective panel on the lower front of the UPS to the left of the bottom two battery shelves.

Figure 3 Input busbars

Output Busbars (Phases are indicated by letters below the bars)

C B A C B A

OUTPUTBYPASS

Remove these links for dual input configuration and wire UPS Main input directly to CB1

Figure 3 Input busbars Rectifier Input Busbars (Phases are indicated by letters below the bars)

The internal batteries are connected with Anderson connectors inside the battery compartment. The batteries are connected to fuses to protect the NX and connected equipment (see Figure 4).

Figure 4 Battery fuses and connections

150A 500V AC/DC

Bussmann

MADE IN USA

150A 500V

MADE IN USA

Internal battery input connections

Battery fuses (fuses are behind access plate on front of UPS; see Note on page 11)

11

Page 17
Image 17
Emerson 208V, 10-30kVA installation manual 2.1.4Cable Connections, Input busbars, Battery fuses and connections