Electrical Connections
Figure 7 Auxiliary terminal block detail (Monitoring Board)
J8
J3J1
LCD
J2
|
|
|
|
|
| Intellislot 2 |
J13 | J21 J25 | J28 | J4 | J26 J30 | J10 | Intellislot 1 |
BFP | INV ACF | EPO | Dry in | MBC | BCB | Intellislot 3 |
| ||||||
| X1 | X2 |
| X3 |
|
|
|
|
|
|
|
J22
J23
J12
J9
J15
J16
J17
X4
J24
X7
X6
PWR |
|
MODEM | X5 |
SNMP CARD |
X4
NOTE: The black square ( ) on each slot indicates Pin 1.
2.3Dry Contacts
The UPS provides input dry contacts and output dry contacts.
2.3.1Input Dry Contacts
There are several input dry contacts at the X3 slot.
Figure 8 Input dry contacts
|
| NOTE: The black square ( ) on each slot indicates Pin 1. | |
Table 1 | Input dry contacts at X3 | ||
|
|
|
|
Position | Name | Description |
|
|
|
|
|
J4.1 | ENV3 | Battery Room Alarm (N.C.) |
|
J4.2 | BtG | Battery Ground Fault Detection (N.C.) |
|
|
|
|
|
J4.3 | GEN1,2 | Generator Join Detection (N.O.) |
|
J4.4 | +12V | +12V Power |
|
|
|
|
|
1 - Must be configured by configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current