5.4Battery Circuit Breaker Box

Options

5.4Battery Circuit Breaker Box

The box contains the same battery isolating circuit breaker as mounted in the battery cabinet.

Two battery circuit breaker boxes are available for use in installations where the battery is not installed in the battery cabinet, in which case the appropriate battery box is fitted as close as possible to the battery and connected to the UPS equipment as illustrated in Figure 27.

The battery circuit breaker box, is required to protect the battery from overcurrents. It also provides electrical isolation between the UPS and the battery, permitting technical service personnel to reduce the risks involved in maintenance work to a minimum.

A separate safety earth must be connected between the UPS unit and circuit breaker box. Two boxes are available depending on the UPS power rating.

Table 7

Available battery circuit breaker boxes

 

 

 

 

Dimensions (in)

 

UPS

H-W-D

Circuit Breaker

10-15 kVA

32.25x20.25x8.3

70A

 

 

 

20-30 kVA

32.25x20.25x8.3

125A

 

 

 

The circuit breaker has the following features:

Short-circuit protection.

Protection against battery cabinet and ups connection errors (polarity reversal +/-).