Specifications and Technical Data
Table 35 Maintenance bypass cabinet dimensions
Unit | Width | Depth | Height |
|
|
|
|
inch | 27.2 | 31.4 | 63 |
|
|
|
|
mm | 690 | 825 | 1600 |
|
|
|
|
Table 36
1+1 Cabinet Type | Width | Depth | Height |
|
|
|
|
1+N Narrow | 27.2 | 31.4 | 63 |
|
|
|
|
Types A00, BR0, CR1, DR1 | 690 | 825 | 1600 |
|
|
|
|
1+N Cabinet Type | Width | Depth | Height |
|
|
|
|
1+N Narrow | 27.2 | 31.4 | 63 |
|
|
|
|
Types A00, E00, J00 | 690 | 825 | 1600 |
|
|
|
|
1+N Wide | 58.5 | 31.4 | 63 |
|
|
|
|
All other types | 1488x | 825x | 1600 |
|
|
|
|
8.2Cable Lengths: Floor to Connection Point Inside UPS
To help calculate the total cable length required, refer to Table 37 for the distance from the floor to selected connection points inside the NX. Determine the cable length required to reach the NX, then add the appropriate length from the table and adequate slack for repair and maintenance.
Table 37 Distance to connection points on the NX UPS
|
| Distance |
| |
|
|
| ||
| From | From | ||
| Floor | Top of Unit | ||
Connection Point on UPS | in. (mm) | in. (mm) | ||
Bypass AC input supply | 30 (750) | 30 | (750) | |
|
|
|
| |
UPS output AC | 30 (750) | 30 | (750) | |
|
|
| ||
Neutral | 11 (280) | 55 (1397 | ||
|
|
| ||
Battery power | 16 (400) | 58 (1474) | ||
|
|
|
|
|
Auxiliary cables: Monitor board (U2) | 60 | (1500) | 20 | (508) |
|
|
|
|
|
Communications | 55 | (1400) | 25 | (635) |
|
|
|
| |
Ground | 8 | (197) | 56 (14227) | |
|
|
| ||
Parallel Board | 70(1780) | 20(508) | ||
|
|
|
|
|
70