Installation Drawings
Figure 37 Lineup
EH
HA
G C
B
D
D
G
E
H
NOTES:
1.All
2.All interconnection cables and hardware supplied by Liebert.
3.AC connections must be made to the UPS module before attaching.
4.See Figure 45 for placement of distribution cabinet.
5.Refer to the individual drawing of each piece of equipment for additional details.
Table 19
Run | From | To | Conductors | |
|
|
|
| |
A | Distribution Cabinet | Load AC Connection | Isolated Ground | |
B | Distribution Cabinet | Load AC Connection | Neutral | |
Distribution Cabinet | ||||
|
|
| ||
C | Distribution Cabinet | Load AC Connection | Ground | |
Distribution Cabinet | ||||
|
|
| ||
D | Distribution Cabinet | Load AC Connection | PH A,B,C | |
|
|
|
| |
E | UPS Module AC Output | Distribution Cabinet | PH A, B, C | |
|
|
|
| |
G | UPS Module AC Output | Distribution Cabinet | Neutral | |
|
|
|
| |
H | UPS Module AC Output | All Ground Connections | Ground | |
|
|
|
|
50