7.0INSTALLATION DRAWINGS

Installation Drawings

7.0INSTALLATION DRAWINGS

The diagrams in this section illustrate the key mechanical and electrical characteristics of the NX UPS System cabinets.

Figure 28 Dimensional view- front and left side views

600

 

 

 

825

 

 

Monitoring

Panel

1600

Air intake area. Do not block air filter.

90

FRONT VIEW

 

LEFT SIDE VIEW

 

 

1. All dimensions are in millimeters.

10mm dia. threaded mounting holes

Leveler

Detail “A” Rear of unit shown without side panel

Manual background Adjustable Stops (see Note 11)

2.A minimum of 24 inches clearance above the unit is required for air exhaust.

3.Installation and service access required. Left-side access recommended for maximum ease of installation.

4.Keep cabinet within 15 degrees of vertical while handling.

5.Top and bottom cable entry available through removal access plates. Remove punch to suit conduit size and replace.

6.Unit bottom is structurally adequate for forklift handling.

7.Open door to replace air filter, washable type, size 354x314.

8.Threaded mounting holes used for seismic anchoring or floor stand. Note: If a floor stand is used, the weight of the unit must be supported under all casters.

9.Each mounting location is supported by two 10 GA. (.135”) galvanized steel. The threaded 12mm insert is approximately 3/4” deep. Mounting bolts must be threaded into unit.

10.Includes side panel. Refer to Detail A for dimension to frame with side panel removed. Side panels are removed between adjacent units that are bolted together.

11.Adjustable stops are not designed to carry the full weight of the cabinet. Finger-tighten stop against the floor, then tighten with a wrench less than two turns for friction against the floor.

42

Page 48
Image 48