UPS Specifications
6.4.1 Battery Manufacturers and Models
Either of two manufacturers’ batteries will be installed in the NX
Table 11 Approved batteries
Battery Manufacturer |
| Models Supplied |
| |
|
|
|
|
|
Enersys Yuasa |
| |||
|
|
|
|
|
C&D Dynasty |
| - | ||
|
|
|
|
|
6.4.2 Input Rectifier
Table 12 Rectifier input power
Rated Power | 10kVA | 15kVA |
| 20kVA |
| 30kVA |
|
|
|
|
|
|
|
Rated Voltage, VAC |
|
| 120/208 |
|
| |
|
|
|
| |||
Supply |
|
| ||||
|
|
|
|
|
| |
Input Voltage Tolerance, VAC (without derating) |
|
|
|
| ||
|
|
|
|
|
| |
Frequency, Hz |
|
| 50 / 60 |
|
| |
|
|
|
|
|
| |
Input Frequency Tolerance % |
|
| ±10 |
|
| |
|
|
|
| |||
Power Factor |
| ≤ 0.99 at full load |
| |||
| ≤ 0.95 at 50% load |
| ||||
|
|
| ||||
Harmonic Current | Less than 4% at full rated UPS output load | |||||
|
|
|
|
|
|
|
Input Current,1 Nominal, A | 28 | 42 |
| 56 |
| 83 |
Output Current, Nominal, A | 28 | 42 |
| 56 |
| 83 |
|
|
|
|
|
|
|
Notes: | 100% Imax <I<125% Imax: 10 min. |
| ||||
1. Overload capacity of input current: |
| |||||
| 125% Imax <I<150% Imax: 1 min. |
|
I>150%: Limits input current immediately
6.4.3 DC Intermediate Circuit
Table 13 DC intermediate circuit
Rated Power | 10kVA | 15kVA |
| 20kVA | 30kVA |
|
|
|
|
| |
| Number of batteries is 24 jars (12V per jar), or 144 cells (2V per | ||||
Recommended number of | cell) for VRLA. The unit is shipped with a nominal voltage of | ||||
| 288VDC. |
|
|
|
|
Recommended float charge voltage |
| 2.27VDC* |
| ||
|
|
|
|
| |
Recommended boost charge voltage |
|
| 2.3VDC* |
| |
|
|
|
| ||
Recommended end of discharge voltage |
|
| |||
|
|
|
|
|
|
Maximum recharge battery current, A | 7.5 | 7.5 |
| 15 | 15 |
|
|
|
|
|
|
Maximum boost charge duration, min.* |
|
| 1440 |
| |
|
|
|
| ||
| 0.1 C default |
| |||
|
|
|
|
| |
Temperature voltage compensation, mV/°C* |
|
| 3 |
| |
|
|
|
|
| |
Ripple voltage superimposed % |
|
| ≤ 1 |
| |
|
|
|
|
|
|
* Set by configuration software and based on usage of VLRA batteries.
40