Emerson 208V, 10-30kVA installation manual Specifications and Technical Data

Models: 10-30kVA 208V

1 80
Download 80 pages 38.9 Kb
Page 69
Image 69
Manual background

Specifications and Technical Data

Table 31 Multi-module bypass cabinet electrical data (continued)

 

 

 

System

System

System

 

 

 

System

 

 

I/P Voltage

Max Input

Input OCP

O/P Voltage

Nominal O/P

Output OCP

Size

Type

kVA

(VAC)

Current

CB Size (A)

(VAC)

Current Rating (A)

CB Size (A)

 

 

30

208

104

125

208

167

225

 

A00, BR0

20

208

70

90

208

111

150

 

15

208

53

70

208

83

125

 

 

2+0

 

10

208

35

45

208

56

70

CR1

30

208

73

100A

208

167

225

 

 

CR1, DR1

30

220

69

100A

208

167

225

 

CR1, DR1

30

480

32

50A

208

167

225

 

CR1, DR1

30

600

25

40A

208

167

225

 

CR1

20

208

110

150A

208

111

150

 

CR1, DR1

20

220

104

150A

208

111

150

 

CR1, DR1

20

480

48

70A

208

111

150

 

CR1, DR1

20

600

38

50A

208

111

150

 

CR1

15

208

146

200A

208

83

125

 

CR1, DR1

15

220

138

200A

208

83

125

 

CR1, DR1

15

480

63

80A

208

83

125

 

CR1, DR1

15

600

51

70A

208

83

125

 

CR1

10

208

219

300A

208

56

70

 

CR1, DR1

10

220

207

300A

208

56

70

 

CR1, DR1

10

480

95

125A

208

56

70

 

CR1, DR1

10

600

76

100A

208

56

70

 

 

30

208

210

300

208

167

225

 

SR0, W00

20

208

140

200

208

111

150

 

15

208

105

150

208

83

125

 

 

 

 

10

208

70

100

208

56

70

63

Page 69