Electrical Connections
2.3.2Maintenance Bypass Cabinet Interface
J26 and J30 are the MBC interface.
Table 2 Maintenance bypass cabinet interface
Position | Name | Description |
|
|
|
J26.1 | T_IT1 | Input transformer over temperature (N.C.) |
J26.2 | AUX_I | Reserved |
|
|
|
J26.3 | +12V | +12V Power |
|
|
|
J26.4 | GND | Power Ground |
|
|
|
J30.1 | FUSE | Reserved |
|
|
|
J30.2 | F_FAN | Fan Fail Alarm (N.C.) |
|
|
|
J30.3 | T_OT1 | Output Transformer Overtemperature (N.C.) |
J30.4 | AUX_O | Reserved |
|
|
|
1 - Must be configured by software before becoming active
NOTE
All auxiliary cables of terminal must be
2.3.3BCB Box Interface
J10 is the BCB box interface.
Table 3 BCB box interface
Position | Name | Description | |
|
|
| |
J10.1 | DRV | BCB Driver Signal - Reserved | |
|
|
| |
J10.2 | FB | BCB Contact State | |
|
|
| |
J10.3 | GND | Power Ground | |
|
|
| |
J10.4 | OL | BCB | |
BCB interface is connected. (N.O.) | |||
|
|
NOTE
All auxiliary cables of terminal must be
NOTE
If BCB interface is connected, a jumper needs to added between Pin 3 and Pin 4.
Figure 9 Jumper connection for BCB interface
UPS Monitoring Board
J10
OL
GND
FB
DRV
Aux – N.O.
Aux – N.O.
Battery Circuit Breaker