Emerson 10-30kVA, 208V Maintenance Bypass interconnection, Installation Drawings

Models: 10-30kVA 208V

1 80
Download 80 pages 38.9 Kb
Page 54
Image 54
Figure 35 Maintenance Bypass interconnection

Installation Drawings

Figure 35 Maintenance Bypass interconnection

Refer to Table 17 for key to interconnection

Maintenance Bypass/Transformer Cabinet

UPS Module

front view without front door and panel

left-side view without side panel

NOTES

1.All Liebert-supplied cable must be repositioned prior to and while the cabinets are being placed in their final installed location.

2.All interconnection hardware supplied by Liebert.

3.AC connections must be made to the UPS module before attaching maintenance bypass/transformer cabinet to UPS module.

4.Utility AC source neutral not required for maintenance bypass/transformer cabinet types D, E, M, N.

5.All cabling will be field-supplied when maintenance bypass/transformer cabinet is configured as stand- alone cabinet.

6.Maintenance bypass/transformer cabinets must attach to the left side only.

7.Refer to the individual drawing of each piece of equipment for additional details.

Table 17 Liebert-supplied interconnect wiring for Maintenance Bypass Cabinet

Run

From

To

Conductors

 

 

 

 

A

Utility AC source

Maintenance

Ph A, B, C bypass/ transformer cabinet

 

 

 

 

B

Utility AC source

Maintenance

Neutral bypass/ transformer cabinet

 

 

 

 

C

Maintenance

UPS module AC input

Neutral - UPS Input

 

 

 

 

D

Maintenance

UPS module AC input

Ph A, B, C - UPS Input

 

 

 

 

E

UPS module AC output

Maintenance

Ph A, B, C - UPS Output

 

 

 

 

F

UPS module AC output

Maintenance

Neutral - UPS Output

 

 

 

 

G

Maintenance

Load AC connection

Neutral bypass cabinet

 

 

 

 

H

Maintenance

Load AC connection

Ph A, B, C bypass cabinet

 

 

 

 

I

Utility AC source

All ground connections

Ground

 

 

 

 

J

Monitoring terminal block

UPS Parallel Logic Board (M3)

Bypass contacts

 

 

 

 

48

Page 54
Image 54