Emerson 10-30kVA 5.2.3Operating Principles Redundancy Paralleling, 5.2.4Operation Modes Summary

Models: 10-30kVA 208V

1 80
Download 80 pages 38.9 Kb
Page 38
Image 38
5.2.3Operating Principles Redundancy Paralleling

Appendix

5.2.3Operating Principles Redundancy Paralleling

The 1+N parallel redundant system can noticeably improve system reliability. In normal condition, none of the UPS modules work at full load. That means that even if the load is increased, the system will not transfer to bypass. And when a UPS module shuts down due to any failure, the remaining UPS modules can still power and protect the load. When redundancy is lost due to module failure or load increase, the parallel system will trigger an alarm.

5.2.4Operation Modes Summary

The parallel system also has operation modes such as normal, battery, bypass and maintenance bypass. All UPS modules in the 1+N parallel system operate in coordination.

Normal Mode Operation

The load is powered by the inverters of all the UPS modules in the system. If the frequency of bypass is within the synchronous range, the inverter will be synchronized with the bypass. Other- wise, the system will operate at nominal frequency.

Battery Mode Operation

The batteries of all UPS modules power the load through their inverters. The system operates at nominal frequency.

Bypass Mode Operation

The condition to transfer to bypass mode is essentially the same as that of single module system. The bypass of all the UPS modules powers the load.

Maintenance Bypass Mode Operation

The sequence to transfer to maintenance bypass mode is the same as for transferring a single- module system. The maintenance bypass switches should be switched on as synchronously as pos- sible. Thus the system can be repaired without interrupting the power supply to critical load.

5.3Installing Parallel System

The basic installation procedure of parallel system is the same as that of single module system. The following sections introduce only the installation procedures specific to the parallel system.

5.3.1Conditions for Parallel System

Each UPS module should have the same rating, the same firmware and hardware version.

Each UPS module must have the same bypass source.

The outputs of all UPS modules are connected altogether.

The main inputs can be from different sources, but the phase rotation sequence of main inputs, bypass inputs and outputs must be correct and the same.

The parallel logic cable and load sharing cable must be connected in a ring correctly (see Figure 23).

5.3.2Cabinet Installation

Parallel system composed of two or more UPS modules using parallel cabinet

The UPS modules that will form the 1+N system should be placed side-by-side. Each battery cabinet is placed next to its corresponding UPS module.

The parallel cabinet should be placed in the middle of the system.

5.3.3Preliminary Checks

Each UPS module should have the same rating, the same firmware and the same hardware version. Refer to the instructions in 5.3.1 - Conditions for Parallel System.

5.3.4Protective Devices

For each UPS, refer to Table 10. For each system, refer to Table 31.