1.WIRING AND TERMINALS
A.HUMIDIFIER CONTROL INFORMATION
(1)See Figure 7 and Figure 9 in Chapter
Table 1. Controller and Sensor Specifications
Power Supply | Operating Voltage | 24 VAC ± 10% |
|
| 50/60 Hz |
|
|
|
| Power Consumption | Max. 3 VA |
|
|
|
| Internal Rectification | |
|
|
|
Signal Inputs | Analog Input | AI1 |
| Input Signal | |
| Resolution | 39 mV, 0.078 mA |
| Accuracy | ± 2% |
|
|
|
| Temperature Input | External Thermistor |
| Range | |
|
|
|
| Humidity Input: |
|
| Range | 0 to 100 %RH |
| Accuracy | ± 3.0% at 25°C (77°F) |
| Repeatability | ± 0.5% |
|
|
|
Signal Outputs | Digital Outputs | DO1 |
| Maximum Load | 24 VAC 2A max. |
|
|
|
Environment | Operation |
|
| Temperature | 0° to 50°C(32° to 122°F) |
| Humidity | <95%RH |
|
|
|
Housing Materials | Cover, back | Fire proof ABS plastic |
| Mounting Plate | Galvanized Steel |
|
|
|