H.SYSTEM MESSAGES AND LIGHTS
(1)Table 3 describes general signal light status meanings.
|
|
| Table 3. Signal Light Status |
|
|
|
|
Yellow | Green | Red |
|
|
|
|
|
OFF | OFF | OFF | Unit is on standby or humidifier has just been energized but has not sensed |
|
|
| production of steam yet. |
|
|
|
|
OFF | ON | OFF | Humidifier senses production of steam. |
|
|
|
|
ON | OFF | OFF | An attention state exists that should not prevent the unit from producing steam |
|
|
| when the controls call for it. Check the message on the screen to try to correct it. |
|
|
|
|
ON | ON | OFF | Prepare to replace cylinder or normal startup operation. May also indicate an |
|
|
| attention during operation. Check the message on the screen to try to correct it. |
|
|
|
|
BLINK | OFF | OFF | Manual Drain On with software drain switch. |
|
|
|
|
OFF | BLINK | OFF | Unit sees a demand, but safeties are open. |
|
|
|
|
OFF | OFF | ON | Operation fault (unit will not run). |
|
|
|
|
(2)Table 4 describes common status messages and the lights displayed for each and their meaning. For a list of warnings and faults, see Chapter
I.DOUBLE UNIT OPERATION
(1)The unit will report only one cylinder at a time if the unit was ordered without coupled circuits. You will notice on the screen the indication of which cylinder you are monitoring and in the lower right the option to monitor the alternate cylinder.