Probable Cause

 

Corrective Action

 

 

 

 

 

 

1.

Is the contactor closed but not energized?

1.

Replace the contactor.

 

2.

Does the processor board display capacity output but

2.

Replace the driver board.

 

 

contactor is open?

 

 

 

 

 

 

 

 

 

 

1.

Back pressure?

 

1.

Verify drain is functioning and clean.

 

2.

Organics present in water?

2.

Verify steam line installation.

 

3.

Insufficient drain or over concentration.

3.

Check optional inline filter.

 

 

 

 

 

 

 

1.

Back pressure?

 

1.

Verify drain is functioning and clean.

 

2.

Organics present in water?

2.

Verify steam line installation.

 

3.

Insufficient drain or over concentration.

3.

Check optional inline filter.

 

 

 

 

 

The cylinder must be

replaced with the same type and

When ordering a new cylinder, quote the model number of

 

model.

 

cylinder presently installed in the humidifier or serial

 

 

 

 

number of humidifier.

 

 

 

 

 

The cylinder must be

replaced with the same type and

When ordering a new cylinder, quote the model number

 

model.

 

presently installed in the humidifier.

 

 

 

 

 

 

1.

Is the drain leaking?

1.

Clean the drain valve.

 

2.

Adjust drain factor.

2.

Set drain factor to 0.7.

 

3.

Check the system backpressure.

3.

Install a fill cup extension kit if required.

 

4.

Is salt required?

 

4.

Add one teaspoon of table salt.

 

 

 

 

 

 

1.

Is the sensor powered?

1.

Use a multimeter to check that the sensor is powered.

 

2.

Is the sensor wiring correct?

2.

Verify wiring is correct as per wiring instructions.

 

3.

Is the sensor defective?

3.

Replace the sensor.

 

4.

Is the RH less than 5%?

4.

RH values under 5% are interpreted as a broken

 

 

 

 

 

sensor.

 

 

 

 

 

 

1.

Is the sensor powered?

1.

Use a multimeter to check that the sensor is powered.

 

2.

Is the sensor wiring correct?

2.

Verify wiring is correct as per wiring instructions.

 

3.

Is the sensor defective?

3.

Replace the sensor.

 

4.

Is the RH less than 5%?

4.

RH values under 5% are interpreted as a broken

 

 

 

 

 

sensor.

 

 

 

 

 

 

1.

Is the sensor powered?

1.

Use a multimeter to check that the sensor is powered.

 

2.

Is the sensor wiring correct?

2.

Verify wiring is correct as per wiring instructions.

 

3.

Is the sensor defective?

3.

Replace the sensor.

 

4.

Is the RH less than 5%?

4.

RH values under 5% are interpreted as a broken

 

 

 

 

 

sensor.

 

 

 

 

 

 

1.

Is the sensor powered?

1.

Use a multimeter to check that the sensor is powered.

 

2.

Is the sensor wiring correct?

2.

Verify wiring is correct as per wiring instructions.

 

3.

Is the sensor defective?

3.

Replace the sensor.

 

4.

Is the RH is less than 5%?

4.

RH values under 5% are interpreted as a broken

 

 

 

 

 

sensor.

 

 

 

 

 

 

---

 

 

To disable this feature, consult the programming manual

 

 

 

 

shipped with the humidifier.

 

 

 

 

 

 

---

 

 

To disable this feature, consult the programming manual

 

 

 

 

shipped with the humidifier.

 

 

 

 

 

 