Nortec NH Series E.Software Initial Self-Test, Self-TestMessages, G.Self-Help, Page 33, 10-20

Models: NH Series

1 92
Download 92 pages 17.56 Kb
Page 40
Image 40
E.SOFTWARE INITIAL SELF-TEST

E.SOFTWARE INITIAL SELF-TEST

 

Table 2. Self-Test Messages

 

 

Graphic Display

Explanation/Comments (What You Read)

 

 

NHTC START-UP:

The unit is beginning its bootup routine, along with powering up the EEPROM on the

INIT CYLINDER

SMART Cylinder

 

 

NHTC START-UP:

The unit reads the type of cylinder to provide maximum control of operation. If it

READING CYLINDER DATA

unable to do so it will skip the rest of the self-test and fault out.

 

 

SELF TEST CYLINDER

Unit energizes the fill valve for 1 second.

Inlet Valve

 

ESC

 

 

 

SELF TEST CYLINDER

Unit energizes the drain valve for 2 seconds.

Drain Valve

 

ESC

 

 

 

SELF TEST CYLINDER

Unit closes the contactor for 2 seconds.

Heat Cont.

 

ESC

 

 

 

SELF TEST CYLINDER

Unit activates the pump (if present) for 2 seconds.

Pump

 

ESC

 

 

 

SELF TEST CYLINDER

Unit activates the bleed valve (if present) for 2 seconds.

Bleed Valve

 

ESC

 

 

 

SELF TEST REMOTE

Unit activates the steam relay for remote fault indication package and green light.

Steam Relay

 

ESC

 

 

 

SELF TEST REMOTE

Unit activates the service relay for remote fault indication package and yellow light.

Service Relay

 

ESC

 

 

 

SELF TEST REMOTE

Unit activates the error relay for remote fault indication package and red light.

Error Relay

 

ESC

 

 

 

SELF TEST REMOTE

Unit activates the unit on relay.

Oper. Relay

 

ESC

 

 

 

F.SOFTWARE FLOW CHART WITH DEFINITIONS

(1)The flow chart in Figure 7 depicts the software logic and definitions.

G.SELF-HELP

(1)The microcomputer applies corrective actions whenever its self-diagnostics identifies a problem that it is able to correct by itself. If the corrective action is not successful then it displays a system message. If the corrective action requires a service person, then the microcomputer’s only resort is to stop the unit and display a system message. The unit never stops unless it has to.

(2)After three days of no call from either the on/off controls or the modulating controls, when active, the three-day drain active feature is automatically activated long enough to drain all water from the steam cylinder. This NORTEC feature will prolong the life of the cylinder. (User selectable, default is ON.)

10-20

Page 33 2008-08-28

Page 40
Image 40