E.SOFTWARE INITIAL SELF-TEST
| Table 2. |
|
|
Graphic Display | Explanation/Comments (What You Read) |
|
|
NHTC | The unit is beginning its bootup routine, along with powering up the EEPROM on the |
INIT CYLINDER | SMART Cylinder |
|
|
NHTC | The unit reads the type of cylinder to provide maximum control of operation. If it |
READING CYLINDER DATA | unable to do so it will skip the rest of the |
|
|
SELF TEST CYLINDER | Unit energizes the fill valve for 1 second. |
Inlet Valve |
|
ESC |
|
|
|
SELF TEST CYLINDER | Unit energizes the drain valve for 2 seconds. |
Drain Valve |
|
ESC |
|
|
|
SELF TEST CYLINDER | Unit closes the contactor for 2 seconds. |
Heat Cont. |
|
ESC |
|
|
|
SELF TEST CYLINDER | Unit activates the pump (if present) for 2 seconds. |
Pump |
|
ESC |
|
|
|
SELF TEST CYLINDER | Unit activates the bleed valve (if present) for 2 seconds. |
Bleed Valve |
|
ESC |
|
|
|
SELF TEST REMOTE | Unit activates the steam relay for remote fault indication package and green light. |
Steam Relay |
|
ESC |
|
|
|
SELF TEST REMOTE | Unit activates the service relay for remote fault indication package and yellow light. |
Service Relay |
|
ESC |
|
|
|
SELF TEST REMOTE | Unit activates the error relay for remote fault indication package and red light. |
Error Relay |
|
ESC |
|
|
|
SELF TEST REMOTE | Unit activates the unit on relay. |
Oper. Relay |
|
ESC |
|
|
|
F.SOFTWARE FLOW CHART WITH DEFINITIONS
(1)The flow chart in Figure 7 depicts the software logic and definitions.
G.SELF-HELP
(1)The microcomputer applies corrective actions whenever its
(2)After three days of no call from either the on/off controls or the modulating controls, when active, the