Table 1. Troubleshooting Symptoms

Table 1. Troubleshooting Symptoms

System

What to Check

Why

 

 

 

Nothing is happening when the

Main power is on and matches the

No, or improper voltage can cause the

on/off switch is turned on

specified voltage on the specification label.

electronics or components not to respond.

 

 

 

 

24 VAC output from the step-down

24 VAC is required to power nearly all the

 

transformer. Check high and low voltage.

components of the humidifier, including the

 

 

electronics.

 

 

 

 

Ensure that fuses in the humidifier and on

The fuses are in place to prevent damage

 

the electronic boards are good. Ensure

to the electronics. If there was a surge the

 

that 24 VAC is getting to the main board.

fuse may have blown to prevent damage

 

 

to the unit.

 

 

 

 

Door interlock open.

The door interlock has malfunctioned.

 

 

 

The unit will not fill or fills very

Water supply is on and water pressure is

The proper water volume and pressure

slowly (less then 1” per minute)

between 30 to 80 psig

must be available as the valves in the NH

 

 

unit rely on its pressure to control volume

 

 

and operation. NORTEC recommends 55

 

 

to 60 PSIG.

 

 

 

 

Unit is getting a demand signal or the unit

The unit will not activate the fill valve

 

is producing the required steam capacity.

without a demand for humidity. It will also

 

See ensuring demand Table 2.

only fill as necessary once there is a

 

 

demand. Once it reaches the requested

 

 

demand, it will stop filling.

 

 

 

 

No leak at drain valve or around cylinder.

The cylinder is held in by gravity and

 

Check for water coming out of the drain.

sealed by an O-ring. If not properly seated,

 

Check the fill valve inlet.

it could leak and prevent the unit from

 

Check fill valve strainer.

filling.

 

Check optional inline filter.

Drain stuck open

 

 

 

 

Pressure in the steam line could also

 

 

prevent filling causing the water in the fill

 

 

cup to overflow to drain.

 

 

Strainer is clogged.

 

 

Fill valve may also be restricted after

 

 

capturing debris in its filter.

 

 

 

Unit will not humidify or is not

Unit is getting a demand signal. Refer to

Unit will not send power to the cylinder

reaching requested capacity.

Table 2.

without a demand and safeties met.

 

 

 

 

Capacity is manually limited.

The unit will not surpass the capacity

 

 

dictated by the user in the software.

 

 

 

 

Cylinder is full.

The unit will not fill further than a full

 

 

cylinder. Operation requires it to try to

 

 

concentrate the conductivity, which may

 

 

take several hours, before it reaches full

 

 

capacity.

 

 

 

Unit has faulted or has a

Check Table 3, Faults and Warning Codes

Each code is identified and each has

warning

 

individual causes and solutions.

 

 

 