Nortec NH Series installation manual Page 65, 10-40, Probable Cause, Corrective Action

Models: NH Series

1 92
Download 92 pages 17.56 Kb
Page 72
Image 72
Page 65 2008-08-28

 

 

Probable Cause

 

Corrective Action

 

 

 

 

 

 

1.

The high limit is too close to the distributor.

1.

Relocate high limit 10 feet from the steam

 

2.

Is there loose wiring?

 

distributor.

 

3.

Are there defective controls?

2.

Check all wires at the safety controls.

 

4.

Is the safety high limit set point is too low?

3.

Replace any defective device.

 

 

 

4.

Change high limit set point to 85% or more.

 

 

 

 

 

 

1.

The high limit is too close to the distributor.

1.

Relocate high limit 10 feet from the steam

 

2.

Is the controller defective?

 

distributor.

 

3.

Are the P and I settings incorrect?

2.

Replace the controller.

 

 

 

3.

Adjust the P and I constants.

 

 

 

 

 

 

1.

The high limit is located too close to the distributor.

1.

Relocate high limit 10 feet from the steam

 

2.

Is the controller defective?

 

distributor.

 

3.

Are the P and I settings incorrect?

2.

Replace the controller.

 

4.

Safety high limit set point is set too low.

3.

Adjust the P and I constants.

 

 

 

4.

Change high limit set point to 85% or more.

 

 

 

 

 

---

 

Contact the system administrator to override the remote

 

 

 

command.

 

 

 

 

 

---

 

To disable this feature, consult the programming manual

 

 

 

shipped with the humidifier.

 

 

 

 

 

 

1.

Is the humidifier oversized?

1.

Reduce manual capacity setting by 50%.

 

2.

Check the sensor location.

2.

The sensor should be located away from doors and

 

3.

Are the P and I settings incorrect?

 

drafts.

 

 

 

3.

Adjust the P and I constants.

 

 

 

 

 

 

1.

Is the humidifier oversized?

1.

Reduce manual capacity setting by 50%.

 

2.

Is the high limit located too close to the distributor?

2.

Relocate the high limit to 10 feet from the steam

 

3.

Are the safety controls damaged?

 

distributor.

 

 

 

3.

Replace any damaged controls.

 

 

 

 

 

 

1.

Is the humidifier still operating?

1.

Verify that the RH setpoint is less than the RH high limit

 

2.

Is the humidifier oversized?

 

setting.

 

 

 

2.

Reduce the manual capacity setting by 50%.

 

 

 

 

 

 

1.

Is the humidifier still operational?

1.

Verify that the RH setpoint is greater than the RH low

 

2.

Is the humidifier oversized?

 

limit setting.

 

 

 

2.

Set the manual capacity setting to 100%.

 

 

 

3.

Add more humidifiers.

 

 

 

 

 

---

 

Verify that the replacement cylinder is the same as the old

 

 

 

cylinder.

 

 

 

 

 

 

1.

Loose wire.

1.

Verify cables.

 

2.

Electronics damaged.

2.

Replace electronics or contact factory.

 

3.

Electromagnetic Interference.

 

 

 

 

 

 

 

10-40

Page 65 2008-08-28

Page 72
Image 72
Nortec NH Series installation manual Page 65, 10-40, Probable Cause, Corrective Action