| Table 1. | NHTC/NHPC Components | |
|
|
|
|
Item Number | Component Name |
| Description |
|
|
|
|
1 | Steam Connector |
| Used to allow easy replacement of cylinders without disconnecting |
|
|
| the steam line. |
|
|
|
|
2 | Condensate Return |
| This inlet is to return condensate to the unit. |
|
|
|
|
3 | Fill Cup |
| The fill cup allows isolation from the fill line by supplying an air gap. |
|
|
| It will also overflow any water that cannot enter the cylinder to drain. |
|
|
|
|
4 | Float Chamber (Optional) |
| Detection OPTION – Used with the advanced foam detection |
|
|
| setting. |
|
|
|
|
5 | Manual Drain Button |
| By pushing this button, manual drain is initiated with software |
|
|
| support. Software support supplies drain cooling if enabled and will |
|
|
| disable manual drain after 10 minutes. |
|
|
|
|
6 | Door Interlock |
| The door interlock prevents the unit from running when the front |
|
|
| door is off. For startup and troubleshooting, pulling this interlock will |
|
|
| overide this safety feature. |
|
|
|
|
7 |
| ||
|
|
| electronic support. |
|
|
|
|
8 | Fill Valve |
| The fill valve allows water to flow up to the fill cup. In units with |
|
|
| Drain Water Cooling to 120 degrees option, this valve is a dual |
|
|
| valve. The second valve is wired in parrallel with the drain valve to |
|
|
| quench the water with fresh cold water everytime the drain is |
|
|
| activated. |
|
|
|
|
9 | Drain Canal |
| The drain canal allows all drainable water to accumulate into one |
|
|
| location to then be drained away. |
|
|
|
|
10 | Drain Valve |
| Drain valve when energized will allow water to flow down to the |
|
|
| drain canal. When not energized, water flowing from the fill cup will |
|
|
| flow up into the cylinder. |
|
|
|
|
11 | Transformer |
| The transformer converts the primary supply voltage to the required |
|
|
| 24 VAC to the unit electronics. It is protected by a fuse to ensure |
|
|
| that the 24 VAC electronics are protected from surges or shorts. |
|
|
|
|
12 | On/Off Switch |
| Turns the unit power on and off. Be aware that high voltage will still |
|
|
| enter the unit even though the 24VAC electronic are disabled. The |
|
|
| contactor will not be energized. Main |
|
|
| any servicing is performed. |
|
|
|
|
13 | Graphical Display and Menu |
| The graphical display and buttons are used to navigate through the |
| Buttons |
| software. Use software flowchart as a reference. |
|
|
|
|
14 | Remote Relay Board (Optional) |
| The remote relay board is a set of 4 dry contacts, rated for 24 VAC |
|
|
| 1A, which activate in conjunction with humidifier on, steam |
|
|
| production, service and error conditions. |
|
|
|
|
15 | NORTEC Cylinder |
| The NORTEC disposable cylinder contains electrodes that become |
|
|
| energized when the contactor is closed. This allows current to pass |
|
|
| through the water from one electrode to another, generating heat |
|
|
| within the water. The water then boils and the output is clean pure |
|
|
| steam. |
|
|
|
|