Table 3. NH System Messages (cont)
NHTC Display Message | LED state | System Action | Symptom Diagnosed |
|
|
|
|
|
|
E17: Req off current | RED | Humidifier interrupts operation | With no system demand, current is |
|
|
| and the fault relay is activated. | detected in the cylinder. |
|
|
|
|
|
|
W18: Foam | YEL | System will activate selected | System has detected foaming and will |
|
|
| foam algorithm. (See Figure 7.) | attempt to self correct if foam mode is |
|
|
|
| active. |
|
|
|
|
|
|
E18: Foam | RED | System will activate selected | System has detected foaming and will |
|
|
| foam algorithm. (See Figure 7.) | attempt to self correct if foam mode is |
|
|
|
| active. |
|
|
|
|
|
|
W19: Cylinder spent | YEL | The electronics allow the | Electronics have determined cylinder |
|
|
| cylinder to be reset up to four | is spent. Within the next 72 hours the |
|
|
| times before locking out the | humidifier will stop. |
|
|
| humidifier. |
|
|
|
|
|
|
|
E19: Cylinder spent | YEL, RED | Humidifier interrupts operation | Electronics have determined that the |
|
|
| and the fault relay is activated. | cylinder is spent. |
|
|
|
|
|
|
W20: Conductivity too low | YEL | Humidifier will continue to | Water conductivity is determined to be |
|
|
| operate on this water supply. | less than optimum. |
|
|
|
|
|
|
W23: Control sensor broken | YEL | Humidifier put on standby. After | Electronics cannot detect the control |
|
|
| a timeout period, this warning | RH sensor connected to the |
|
|
| becomes a fault. | humidifier. |
|
|
|
|
|
|
E23: Control sensor broken | RED | Humidifier interrupts operation | Electronics cannot detect the control |
|
|
| and the fault relay is activated. | RH sensor connected to the |
|
|
|
| humidifier. |
|
|
|
|
|
|
W24: Limit sensor broken | YEL | Humidifier put on standby. After | Electronics cannot detect the limit RH |
|
|
| a timeout period, this warning | sensor connected to the humidifier. |
|
|
| becomes a fault. |
|
|
|
|
|
|
|
E24: Limit sensor broken | RED | Humidifier interrupts operation | Electronics cannot detect the limit RH |
|
|
| and the fault relay is activated. | sensor connected to the humidifier. |
|
|
|
|
|
|
W25: | YEL | The humidifier drains the | This safety feature drains standing |
|
activated |
| cylinder after three days of | water. |
|
|
| inactivity. |
|
|
|
|
|
|
|
W26: | YEL | The humidifier drains the | This customer selected feature drains |
|
activated |
| cylinder after three days of | the cylinder to remove minerals. |
|
|
| operation. |
|
|
|
|
|
|
|