C. HUMIDIFIER MANDATORY PRE-START UP CHECKLIST

C. HUMIDIFIER MANDATORY PRE-START UP CHECKLIST

 

Unit Serial #: _________________No. of humidifiers: _______

Tag: _______________

Unit type: _______

__________Voltage: _____V/___ph

Steam output: ____lbs/hr

Customer/Job: ______________ Address: _____________________________

Inspected by: ________________Date of inspection: ____/____/____

 

 

 

 

 

WATER QUALITY:

 

 

 

 

Well water ___

City water ___

Softened water ___

RO / DI water ___

Conductivity: _______ mhmos

Hardness: _____ gr.

 

HUMIDIFIER MOUNTING:

 

 

 

Clearances around the unit

Acceptable

Obstruction

– Front (door opens freely?)

3 ft min. ______________________

– Top (steam lines)

 

2 ft min. ______________________

– Bottom (fill, drain, controls)

2 ft min. ______________________

– Right (main pwr)

 

2 ft min. ______________________

STEAM LINES:

 

CONDENSATE LINES:

– Slope up 2 in. per 12 in. ___

 

– Sloped back to drain ___

– Slope down 0.500 in. per 12 in. ___

– Trapped 2 in. more than static

– Traps ___

 

 

duct pressure ___

– Insulated ___

 

 

– Size _______

– Length/Size _____/_______

 

– Stainless steel ___ or plastic ___

 

 

 

– ____% Vertical ____% Horizontal

– 90 degree elbows ___ qty: ____ – 45 degree Elbows ___ qty: ____

– Can condensate be trapped anywhere in the steam line? yes ___ no ___

WATER LINES:

 

 

 

– 0.050 in. at max 4ft from the unit ___ – 3/8 in. connection at fill G

 

– Water pressure: 30-80 psig ___

– PVC ___

– Stainless steel ___

DRAIN LINES:

 

 

 

– Air gap located within 3 ft of the unit ___ – Sloped to drain ___

– Size:________

CYLINDER:

– Cylinder properly installed and sitting upright

WIRING:

– No loose wires around the unit or on the PC board? yes ___ no ___

CONTROLS:

 

Installed Location / Wiring /Setting

Installed Location / Wiring /Setting

– High limit: ___ ____________________ – Air proving: ___ ____________________

– Mod controller: ___ ________________– Other: ___ ________________________

POWER:

Voltage, amperage rating and fuse correspond to Spec Label: ___

Disconnect switch located close to humidifier: ___