![C. HUMIDIFIER MANDATORY PRE-START UP CHECKLIST](/images/new-backgrounds/51085/51085157x1.webp)
C. HUMIDIFIER MANDATORY |
| |||
Unit Serial #: _________________No. of humidifiers: _______ | Tag: _______________ | |||
Unit type: _______ | __________Voltage: _____V/___ph | Steam output: ____lbs/hr | ||
Customer/Job: ______________ Address: _____________________________ | ||||
Inspected by: ________________Date of inspection: ____/____/____ | ||||
|
|
|
|
|
WATER QUALITY: |
|
|
|
|
Well water ___ | City water ___ | Softened water ___ | RO / DI water ___ | |
Conductivity: _______ mhmos | Hardness: _____ gr. |
| ||
HUMIDIFIER MOUNTING: |
|
|
| |
Clearances around the unit | Acceptable | Obstruction | ||
– Front (door opens freely?) | 3 ft min. ______________________ | |||
– Top (steam lines) |
| 2 ft min. ______________________ | ||
– Bottom (fill, drain, controls) | 2 ft min. ______________________ | |||
– Right (main pwr) |
| 2 ft min. ______________________ | ||
STEAM LINES: |
| CONDENSATE LINES: | ||
– Slope up 2 in. per 12 in. ___ |
| – Sloped back to drain ___ | ||
– Slope down 0.500 in. per 12 in. ___ | – Trapped 2 in. more than static | |||
– Traps ___ |
|
| duct pressure ___ | |
– Insulated ___ |
|
| – Size _______ | |
– Length/Size _____/_______ |
| – Stainless steel ___ or plastic ___ | ||
|
|
| – ____% Vertical ____% Horizontal |
– 90 degree elbows ___ qty: ____ – 45 degree Elbows ___ qty: ____
– Can condensate be trapped anywhere in the steam line? yes ___ no ___
WATER LINES: |
|
|
|
– 0.050 in. at max 4ft from the unit ___ – 3/8 in. connection at fill G |
| ||
– Water pressure: | – PVC ___ | – Stainless steel ___ | |
DRAIN LINES: |
|
|
|
– Air gap located within 3 ft of the unit ___ – Sloped to drain ___ | – Size:________ |
CYLINDER:
– Cylinder properly installed and sitting upright
WIRING:
– No loose wires around the unit or on the PC board? yes ___ no ___
CONTROLS: |
|
Installed Location / Wiring /Setting | Installed Location / Wiring /Setting |
– High limit: ___ ____________________ – Air proving: ___ ____________________
– Mod controller: ___ ________________– Other: ___ ________________________
POWER:
–Voltage, amperage rating and fuse correspond to Spec Label: ___
–Disconnect switch located close to humidifier: ___