Emerson MRLDS Mrlds Gateway Setup on I/O Network, Gateway Connections, Gateway Board

Models: MRLDS

1 20
Download 20 pages 16.66 Kb
Page 13
Image 13

bits with no parity and 2 (two) stop bits.

Register

PDU

Logical

Range

Name

Address

Address

 

Fault and

0x0000

1

Under Range

Module

 

 

2 (msb)

State

 

 

 

 

 

 

 

 

 

 

Under Volt-

 

 

 

age 8 (msb)

 

 

 

Temperature

 

 

 

10 (msb)

 

 

 

Lamp Fail

 

 

 

40 (msb)

 

 

 

Test Mode

 

 

 

80 (msb)

 

 

 

Warm Up

 

 

 

Complete

 

 

 

0 (Lsb)

 

 

 

Cal/Setup

 

 

 

2 (Lsb)

 

 

 

Factory

 

 

 

Mode

 

 

 

4 (Lsb)

 

 

 

Trouble

 

 

 

Mode

 

 

 

8 (Lsb)

Gas

0x0001

2

0 to 40

Number

 

 

 

Gas Con-

0x0002

3

-20 to 1050

centration

 

 

(ppm)

Gas

R-22 = 6

 

 

Numbers

R-404A = 27

 

 

 

R-134a = 15

 

 

Table 4-3- RS485 Output Specifications

4.3MRLDS Gateway

4.3.1MRLDS Gateway Setup on I/O Network

Modbus versions of the MRLDS must be connected to the 810-3040 MRLDS Gateway. The MRLDS Gateway can be mapped in either of two ways: it can be set up on I/O Net as an IRLDS application or as a 16AI board. Select by setting the Gateway’s dip switch #5 to the OFF or ON position (Figure 4-6).

SELECT I/O NET MODE

OFF = IRLDS

ON = 16AI

ON

OFF = IRLDS ON = 16AI

Figure 4-6- I/O Network Modes

4.3.2Gateway Connections

Up to 12 MRLDS units may be connected to the Gate- way board (P/N 810-3040). The Gateway board can inter- face with a site controller as a 16AI or as an IRLDS. If the site controller is an Einstein or E2, it is recommended to interface them as an IRLDS. Multiple Gateways can be used, each with up to 12 connected MRLDS units.

4.3.3The Gateway Board

Figure 4-7- MRLDS Gateway Board Layout (810-3040)

MRLDS Gateway

MRLDS Modbus Version (809-101x) 7

Page 13
Image 13
Emerson MRLDS operation manual Mrlds Gateway Setup on I/O Network, Gateway Connections, Gateway Board