ways.
Navigate to the controller’s Input Status screen and highlight the board and point that you wish to map. Press F1 to go to the Input Setup screen for that board/point. Each point will increase incrementally to correspond with each board. (For example, where the MRLDS is address 1 and the MRLDS address is 100, use board 1, point 1. For an MRLDS address of 101, use point 2.)
4.4.3E2/Einstein Controllers
Next, set up the following parameters on the Input Setup screen:
•Sensor Type: Linear
•Low End Point: 0.00000
•Select Eng. Units: PPM
•HighEnd Point: 4.80000
•High Eng. Units: 1200.0000
Figure 4-20 - Analog Input Screen Settings Example for E2
4.4.4RMCC Controllers Version 2.1 and Newer
4.4.4.1REFLECS Setup for IRLDS IIs
Set dip switch 8 to ON and follow the steps for setting up IRLDS IIs through the REFLECS controller interface:
1.Log on.
2.Press 7 for Configuration to reach the CON- FIGURATION screen.
Input Definitions should be set here to show how the sensor control is linked to the zone. The number of devices and IRLDS IIs are connected to the Gateway and enabled is the number of address slots the Gateway will use.
3.Press 1 for Input Definitions to reach the INPUT DEFINITIONS screen.
4.Pressing the down arrow several times will get you to the input list of
The board number for the IRLDS II setup is the address of the Gateway. If there are three or less IRLDS II control- lers connected to a Gateway, the Gateway address = the IRLDS II address. However, if there are more than three IRLDS controllers, the second Gateway address will be the one entered for the board number, but the IRLDS II con- trollers are set 1 to 3 on the second Gateway.
5.Press 0 (zero) to go back to the CONFIGU- RATION screen.
6.Press 7 for I/O Brd Setup to reach the I/O BOARD MENU screen.
7.Press 2 to Set Device #’s.
The Gateway will react as three 16AI boards. The num- ber of IRLDS II controllers plus the real number of 16AIs
=the total number of 16AIs to enter in the next step:
8.At the I/O BOARD DEVICE NUMBERS screen, press the down arrow key to reach Number 16AI Boards and enter the number of how many 16AI boards and IRLDS II con- trollers there are. Press Enter.
9.Arrow down to the I/O BOARD MENU and press 0 (zero) twice to go back to the MAIN MENU screen.
10.Press 4 for Sensor Control.
11.Press 2 for
12.Press the right arrow to move to the Name
12 • MRLDS I&O Manual |