Emerson MRLDS operation manual Input Definitions, Sensor Setup, Sensor Setpoints

Models: MRLDS

1 20
Download 20 pages 16.66 Kb
Page 19
Image 19

field to change the name, and press the down or right arrow to move to the (sensor) Type field. Use the “.” and keys to scroll through the options and select IRLDS. (The Gain and Offset parameters are automatically configured for you.)

13.Use the arrow keys to move off the active fields and press 0 (zero) twice to go back to the main screen.

4.4.5BEC and RMCC Controllers Less Than Version 2.1

4.4.5.1Input Definitions

Locate the screens in the BEC or RMCC that are used to define input board and points. This is usually achieved by pressing 7 then 1 from the Main Menu. Press the DOWN ARROW key several times until the SENS01- SENS08 inputs are shown.

The 16AI connected to the IRLDS’s output terminals must be set up in the REFLECS’s system software. If the 16AI was given a unique board number by setting the dip switch S3, and wired to the terminals so that each zone number corresponds to a 16AI point number (zone 01 con- nected to point 01, for example), these board and point ad- dresses must now be entered into the REFLECS.

The screen above shows how the board and point ad- dresses for zone 1 would be set up for a 16AI board num- bered 1. Both SENS01 and SENS02 are set up as 01:01 so that SENS01 can monitor concentration and SENS02 can monitor fault status.

Set up the remaining sensors using the instructions giv- en above. For each point on the 16AI, set up two sensors with the same addresses.

4.4.5.2Sensor Setup

 

SENSOR SETUP

 

12:00

 

 

 

 

 

#:01

Status:OFF

Name:REFR LK ZN 01

 

 

Type: Linear

 

 

 

 

(T)mp (1)00 (5)00 (R)fLeak (K)Watt

 

 

(H)um (2)00 (D)ig (L)inear L(Q)Lev

 

 

(6)450 Tmp

Dew(P)nt

 

 

 

Logging Interval (HH:MM:SS):

00:03:00

 

 

=PREV

=NEXT ->=SET-DATA

0=MENU

 

 

 

 

 

 

 

Locate the screen in the BEC or RMCC where sensors are set up. This is usually a menu option in the Sensors Menu, which may be reached from the Main Menu.

The 0-4.8V signal is a linear signal representing a mea- sured concentration of 0-1200 ppm, and a voltage of 5.0V indicates a fault. In order for the REFLECS to read these voltages correctly, the REFLECS sensor inputs must be configured as linear sensors.

Name

A name for the sensor input may be entered in the Name field. Since each IRLDS zone is set up with two REFLECS sensor inputs, choose names for each input that distinguish the input’s function. For example, the sensor input set up to read leak concentrations on zone 1 should have a name like REFR LK ZN 01, and the input set up to monitor fault sta- tus should have a name like FAULT ZN 01.

Type

All sensor inputs connected to an IRLDS should be set up as linear sensors. Enter (L)inear in the Type field.

Logging Interval

The logging interval is the amount of time between log entries in the REFLECS’s Data Log.

When choosing a logging interval, keep in mind the amount of time it takes an IRLDS to go through an entire cycle of samplings. For example, a 16-valve IRLDS with 30 second sampling times for each zone takes a total of eight minutes to sample all zones. Choosing a logging in- terval smaller than the IRLDS’s cycle time will simply clutter the REFLECS data log with multiple copies of the same sample.

4.4.5.3Sensor Setpoints

 

 

 

 

 

 

 

 

 

SENSOR

SETPOINTS

LINEAR INPUT

12:00

 

 

#:01

Status:OFF

Name:REFR LK ZN 01

 

 

Stay

ON for:000

min

Eng.Unit:PPM

 

 

Using Diff

Of 01

00

00

00

 

 

 

0

Of 0

0

0

0

 

 

Gain 250

 

Offset

00000 mv

 

 

ON: 0

Dly: 0000 OFF:0

Dly:0000

 

 

=PREV

=NEXT ->=SET-DATA

0=MENU

 

 

 

 

 

 

 

 

 

Locate the screen in the BEC or RMCC where sensor set points are specified. This is usually a menu option in the Sensors Menu, which may be reached from the Main Menu.

After the linear sensors have been set up, the REFLECS must be told how to interpret the linear voltage given by the

IRLDS.

Eng. Unit

The REFLECS does not require any specific engineer- ing unit to be specified for sensor values. However, for eas- ier reading of status screens and data logs, “PPM” should be entered for sensor inputs that read concentration, and

Controller Setup for Modbus MRLDS

MRLDS Modbus Version (809-101x) 13

Page 19
Image 19
Emerson MRLDS operation manual Input Definitions, Sensor Setup, Sensor Setpoints