Installation Drawings
TOP ENTRY NOTES:
1.Cables from lower busbars must be routed and tied to the aligning holes on the the cable landing bar directly above (see figure below). Installation method is to prevent cables from lower busbars from contacting the upper busbars.
2.Cables from upper busbars can be optionally tied also, as shown in top entry view.
3.The UPS output phase cables must be run
on the left side of cabinet, outside of the ground bus.
Input | Neutral |
Ground | Output |
Phase B |
Input
Phase C
Input
Phase A
UPS
Output
Phases
BOTTOM ENTRY NOTES:
1.Cables from upper busbars must be routed so that they run clear of lower busbars.
Output
Phase A
Output
Phase C
DO NOT
TWO LUGS ON SAME SIDE OF BUSBAR).
THIS IS TO PREVENT THE CABLES
FROM COMING INTO CONTACT WITH
OTHER BUSBARS.
Maintenance
Isolation Breaker
(MIB) Busbar
TOP CABLE ENTRY ROUTING | BOTTOM CABLE ENTRY ROUTING |
BREAKERS REMOVED FOR CLARITY
15