Emerson UPS Systems installation manual Installation Drawings

Models: UPS Systems

1 36
Download 36 pages 16.53 Kb
Page 25
Image 25

Installation Drawings

Table 3 Liebert-supplied interconnect wiring for three-input Liebert NXL Maintenance Bypass Cabinet

Run

To

From

Conductor

 

 

 

 

A

Utility AC - Phase A

MBC Bypass AC - Phase A

Maintenance Bypass AC - Phase A

 

 

 

 

B

Utility AC - Phase B

MBC Bypass AC - Phase B

Maintenance Bypass AC - Phase B

 

 

 

 

C

Utility AC - Phase C

MBC Bypass AC - Phase C

Maintenance Bypass AC - Phase C

 

 

 

 

D

Utility Neutral

MBC Neutral

System Input Neutral

 

 

 

 

E

Utility Ground

MBC Ground

System Ground

 

 

 

 

F

Utility AC - Phase A

UPS Bypass AC - Phase A

UPS Bypass Input - Phase A

 

 

 

 

G

Utility AC - Phase B

UPS Bypass AC - Phase B

UPS Bypass Input - Phase B

 

 

 

 

H

Utility AC - Phase C

UPS Bypass AC - Phase C

UPS Bypass Input - Phase C

 

 

 

 

I

Utility AC - Phase A

UPS Rectifier AC - Phase A

UPS Rectifier Input - Phase A

 

 

 

 

J

Utility AC - Phase B

UPS Rectifier AC - Phase B

UPS Rectifier Input - Phase B

 

 

 

 

K

Utility AC - Phase C

UPS Rectifier AC - Phase C

UPS Rectifier Input - Phase C

 

 

 

 

L

Utility Neutral

UPS Neutral

UPS Neutral

 

 

 

 

M*

MBC Ground

UPS Equipment Ground

UPS Ground

 

 

 

 

N

UPS Output AC - Phase A

MBC Output AC - Phase A

UPS Output - Phase A

 

 

 

 

O

UPS Output AC - Phase B

MBC Output AC - Phase B

UPS Output - Phase B

 

 

 

 

P

UPS Output AC - Phase C

MBC Output AC - Phase C

UPS Output - Phase C

 

 

 

 

P1

UPS Output Neutral

MBC Neutral

UPS Neutral

 

 

 

 

Q

MBC Output AC - Phase A

Load AC - Phase A

Load AC Input - Phase A

 

 

 

 

R

MBC Output AC - Phase B

Load AC - Phase B

Load AC Input - Phase B

 

 

 

 

S

MBC Output AC - Phase C

Load AC - Phase C

Load AC Input - Phase C

 

 

 

 

T

MBC Neutral

Load Neutral

Load Neutral

 

 

 

 

U

MBC Ground

Load Ground

Load Equipment Ground

 

 

 

 

V

MBC Terminal Strip

UPS External Interface Board

Control Wiring

 

 

 

 

* For detached units only

21

Page 25
Image 25
Emerson UPS Systems installation manual Installation Drawings