Installation Drawings

Figure 15 Liebert NXL Maintenance Bypass Cabinet Control wire diagram without interlock

Connections at UPS External

Interface Board (EIB) 1 3

02-806708

 

 

TB0821

 

 

 

TB0811

3

 

 

1

1

3

TB0813

3

1

 

 

 

TB0824

 

LOW VOLTAGE

TERMINAL STRIP

- TB1 -

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

TB1-13 TB1-12 TB1-11

TB1-10

TB1-9

TB1-8 TB1-7 TB1-6

TB1-5 TB1-4 TB1-3 TB1-2

TB1-1

TB0813

TB0811

TB0823

TB0821

EPO PB SW

Table 4

Control wiring connections without

 

interlock

 

 

 

 

From

To

Purpose

 

 

 

TB1-1

Customer EPO

 

Push Button Switch

 

 

EPO Signal

TB1-2

Customer EPO

 

Push Button Switch

 

 

 

 

 

 

TB1-3

TB0821-2

Maint. Bypass Enable

TB1-4

TB0821-1

Contacts

 

 

 

TB1-5

TB0824-3

 

 

 

 

TB1-6

TB0824-2

UPS REPO Contacts

 

 

 

TB1-7

TB0824-1

 

 

 

 

TB1-8

TB0811-3

 

 

 

 

TB1-9

TB0811-2

MIB Contacts

WIRE DIAGRAM WITHOUT INTERLOCK

TB1-10

TB0811-1

 

TB1-11

TB0813-3

 

 

 

 

TB1-12

TB0813-2

MBB Contacts

 

 

 

TB1-13

TB0813-1

 

22

Page 26
Image 26
Emerson UPS Systems installation manual Control wiring connections without, Interlock