Emerson UPS Systems Top View Door Open, Bottom Conduit Plates, Bottom View Footprint

Models: UPS Systems

1 36
Download 36 pages 16.53 Kb
Page 15
Image 15
KNOCK-OUT FOR CONTROL WIRING O 1"
2 PLCS
24.2
(615)

Installation Drawings

Figure 7 Liebert NXL Maintenance Bypass Cabinet—250 and 300kVA outline drawing

 

 

31.3

24.0

CONDUIT

( 795)

4.9

( 610)

LANDING

24.8

AREA

( 124)

TYP

( 630)

 

56.8

21.1

3.9

( 1442)

( 100)

 

( 535)

TYP

 

 

KNOCK-OUT FOR

 

 

CONTROL WIRING

 

 

O 1"

 

 

3 PLCS

 

BOTTOM VIEW (FOOTPRINT)

TOP VIEW (DOOR OPEN)

 

 

 

76.8 ( 1951)

CG

12.2

(309)

38.5 ( 979)

33.5 ( 850)

CG

38.5 ( 979)

22.7 ( 578)

NOTES:

1.All dimensions are in inches (mm).

2.24" minimum clearance above unit required for air exhaust.

3.Keep cabinet within 15 degrees of vertical while handling.

4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.

5. Unit bottom is structurally adequate for forklift handling.

6. Includes side panel. Side panels are removed between adjacent units which are bolted togethe r.

7.Control wiring and power wiring must be run in separate conduits.

8.Aluminum and copper-clad aluminum cables are not recommended.

9.All wiring is to be in accordance with national and local electrical codes.

10.Widths are without side panels. The width is 25.6" (650mm) with side panels.

11.The depth dimension includes the front door and rear panel.

21.9

CONDUIT

( 555)

LANDING

 

AREA

 

16.1

 

( 410)

BOTTOM CONDUIT PLATES

11

Page 15
Image 15
Emerson UPS Systems Top View Door Open, Bottom Conduit Plates, Bottom View Footprint, Installation Drawings