Empire Comfort Systems 3)(N, 1, 2 VENTING FIREPLACE - TOP continued, Below Grade Installation

Models: 2 1 DVD32FP3 3)(N

1 60
Download 60 pages 21.3 Kb
Page 19
Image 19
VENTING FIREPLACE - TOP (continued)

VENTING FIREPLACE - TOP (continued)

Below Grade Installation

When it is not possible to meet the required vent terminal clearances of 12" (305 mm) above grade level, a snorkel kit is recommended. It allows installation depth down to 7" (178 mm) below grade level. The 7" (178 mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall.

Ensure the sidewall venting clearances are observed. If venting system is installed below ground, we recommend a window well with adequate and proper drainage to be installed around the termination area.

TYPICAL BASEMENT INSTALLATION

Figure 21

Examples of possible venting systems using one (1) 90° elbow. Eight (8) feet is listed as minimum vertical vent run with 20 feet of maximum horizontal vent run. Vertical dimensions are based on centerline to centerline of pipe. Horizontal dimensions are based on centerline of pipe to end of termination.

Firestop at

Ceiling LevelBelow Grade Installation

Figure 22

Examples of possible venting systems using two (2) 90° elbows. V is listed as minimum vertical dimensions and H1 + H2 is listed as total of maximum horizontal dimensions. The maximum vertical and horizontal distances for two (2) 90° elbows as shown in Figure 23 is 20 feet (6.1 m).

Attention: Refer to Figure 20 for additional venting requirements.

Firestop at

Ceiling Level Manual background

23552-4-0408

Figure 23

Page 19

 

Page 19
Image 19
Empire Comfort Systems 3)(N, 1, DVD32FP3 VENTING FIREPLACE - TOP continued, Below Grade Installation