035-17233-000-C-0702

Check all connections for leaks when piping is completed, using a soap solution. NEVER USE A FLAME.

VENT AND COMBUSTION AIR HOODS

Two vent hoods and a combustion air hood (with screens) are shipped attached to the blower housing in the blower com- partment. These hoods must be installed to assure proper unit function. All hoods must be fastened to the outside of the gas heat access panel with the screws provided in the bag also attached to the blower housing.

The screen for the combustion air intake hood is secured as shown on the label attached to the hood. The top flange of this hood slips in under the top of the access panel opening when installing. Refer to Figure 8.

Each vent hood is installed by inserting the top flange of the hood into the slotted opening in the access panel and secur- ing in place.

The outdoor and return air dampers, the damper actuator, the damper linkage, the outdoor and return air divider baffles, and all the control sensors are factory mounted as part of the Factory installed economizer option.

ENTHALPY SET POINT ADJUSTMENT

Remove the economizer access panel from the unit to check the following adjustments. Loosen but do not remove the two

panel latches.

Extreme care must be exercised in turning both the setpoint and minimum position adjusting screws to prevent twisting them off.

1.The enthalpy set point may now be set by selecting the desired setpoint shown in Figure 9. Adjust as follows:

For a single enthalpy operation, carefully turn the set point adjusting screw to the A, B, C or D setting corre- sponding to the lettered curve.

For a dual enthalpy operation, carefully turn the set point adjusting screw fully clockwise past the D setting.

VENT AIR

OUTLET

HOODS

COMBUSTION AIR INTAKE HOOD

SLOTTED OPENINGS IN ACCESS PANEL

GAS HEAT

ACCESS

PANELS

2.To check that the damper blades move smoothly without binding, carefully turn the minimum position adjusting screw fully clockwise and then energize and de-energize terminals R to G. With terminals R to G energized, turn the minimum position screw counterclockwise until the desired minimum position has been attained.

3.Replace the economizer access panel. Reposition the two latches horizontally and retighten the screws.

POWER EXHAUST/BAROMETRIC RELIEF DAMPER AND RAIN HOOD OPTION

The instructions for the power exhaust/barometric relief damper and rain hood can be found in form 44-320-10. The exhaust fan, all supporting brackets, angles, and the wiring are factory installed as part of the power exhaust option.

FIGURE 8 : VENT AND COMBUSTION AIR HOODS

OPTIONAL ECONOMIZER/MOTORIZED DAMPER RAIN HOOD

The instruction for the optional economizer/motorized damper rain hood can be found in form 44-320-2. Use these instructions when field assembling an economizer rain hood onto a unit.

All of the components, including the dampers, hardware, and mounting instructions are shipped in a single package exter- nal from the unit. The hood must be field assembled and installed.

Power exhaust is not available as a field installed option.

Unitary Products

11

Page 11
Image 11
Energy Tech Laboratories DHG180 Vent and Combustion AIR Hoods, Power EXHAUST/BAROMETRIC Relief Damper and Rain Hood Option

DHG180, DHG240 specifications

Energy Tech Laboratories has made significant strides in the realm of energy efficiency and renewable technologies with the introduction of their innovative models, the DHG240 and DHG180. These advanced devices are designed to optimize energy consumption, minimize environmental impact, and enhance overall energy management.

The DHG240 model stands out with its high-capacity performance, delivering a robust output of 240 kW. This unit is ideal for large facilities and industrial applications, where energy demands are high. One of its main features is its advanced algorithm for energy distribution, which allows for optimal load balancing across various operational units. This ensures that energy is used efficiently, reducing waste and lowering operational costs.

Similarly, the DHG180 is designed for medium-sized operations, providing an output of 180 kW. It offers an effective solution for businesses seeking to improve energy efficiency without the excessive overhead costs typically associated with larger systems. The DHG180 incorporates state-of-the-art monitoring systems that provide real-time data on energy consumption, allowing operators to make informed decisions and adjust settings as needed.

Both models integrate cutting-edge technologies such as smart grid capabilities and renewable energy sources. They are equipped to handle integration with solar panels and wind turbines, enabling facilities to harness clean energy and reduce reliance on fossil fuels. This feature not only contributes to sustainability goals but also provides a buffer against fluctuating energy prices.

The design of both the DHG240 and DHG180 prioritizes durability and reliability. They are constructed from high-quality materials that withstand harsh operational conditions, ensuring a long lifespan and reduced maintenance costs. Furthermore, these systems are compliant with various energy efficiency standards, making them a responsible choice for environmentally conscious businesses.

User-friendliness is another hallmark of these devices. An intuitive interface allows operators to easily monitor and control energy usage, while remote access compatibility enables management from off-site locations. This flexibility is crucial in today’s fast-paced business environment.

In conclusion, Energy Tech Laboratories’ DHG240 and DHG180 models represent the forefront of energy technology. By delivering high performance, integrating renewable solutions, and prioritizing ease of use, these units empower businesses to achieve their energy efficiency goals while promoting sustainability. Whether for large industries or medium-sized enterprises, these systems are engineered to meet the dynamic needs of modern energy management.