TABLE 6: PHYSICAL DATA

035-17233-000-C-0702

TABLE 6: PHYSICAL DATA

 

MODELS

 

DHG

 

 

 

 

 

 

 

180

240

 

 

 

 

 

EVAPORATOR

Centrifugal Blower (Dia. x Wd. in.)

15 x 15

18 x 15

BLOWER

 

 

 

Fan Motor HP

5

7.5

 

 

 

 

EVAPORATOR

Rows Deep

4

4

 

 

 

 

Fins Per Inch

13.5

13.5

COIL

 

 

 

 

 

Face Area (Sq. Ft.

15.5

20.0

 

 

 

 

CONDENSER

Propeller Dia. (in.) (Each)

30

30

 

 

 

 

FANS

Fan Motor Hp (Each)

1

1

(Two Per Unit)

 

 

 

 

Nom. CFM (Each)

5765

7000

 

 

 

 

 

CONDENSER

Rows Deep (Each)

3

3

 

 

 

 

COILS

Fins Per Inch (Each)

13

15

(Two Per Unit)

 

 

 

 

Face Area (Sq. Ft.) (Total)

36.0

43.3

 

 

 

 

 

COMPRESSOR

10-Ton Tandem Hermetic Recip.

11

2

(Qty. Per Unit)

 

 

 

 

5-Ton Hermetic Recip.

1

-

 

 

 

 

 

 

Quantity Per Unit (16” X 20” X 2”)

-

4

 

 

 

 

AIR

Quantity Per Unit (16” X 25” X 2”)

-

4

FILTERS

 

 

 

Quantity Per Unit (18” X 24” X 2”)

5

-

 

 

 

 

 

Total Face Area (sq. ft.)

15.0

20.0

 

 

 

 

 

CHARGE

Refrigerant 22

System #1

29/9

23

(lbs./oz.)

 

 

 

System #2

14/8

23/12

 

 

 

 

 

 

BASIC

DHG

240Mbh (lbs)

2100

2300

UNIT

(Gas/Electric)

 

 

 

320Mbh (lbs)

2140

2340

 

 

 

 

 

 

Economizer

(lbs)

160

 

 

 

 

OPTIONS

Economizer with

245

Power Exhaust (lbs)

 

 

 

 

 

 

 

Motorized Damper (lbs)

150

 

 

 

 

 

Roof Curb (lbs)

175

185

ACCY.

 

 

 

Barometric Damper (lbs)

45

45

 

 

 

 

 

Wood Skid (lbs)

220

220

 

 

 

 

 

1This compressor will be energized first.

TABLE 7: DHG VOLTAGE LIMITATIONS1

POWER SUPPLY

 

VOLTAGE

 

 

 

 

MIN.

 

MAX.

208/230-3-60

187

 

253

 

 

 

 

460-3-60

414

 

506

 

 

 

 

575-3-60

518

 

506

 

 

 

 

1Utilization Range “A” in accordance with ARI Standard

110.

TABLE 8: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

36”

 

 

Back

24” (Less Economizer)

49” (With Economizer

 

 

 

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

 

 

 

Right Side (Cond. Coil)

36”

 

 

Below Unit1

0”

 

72” With 36” Maximum

Above Unit2

Horizontal Overhang (For

 

Condenser Air Discharge)

 

 

1Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.

2Units must be installed outdoors. Overhanging struc- tures or shrubs should not obstruct condenser air dis- charge outlet.

TABLE 9: DHG ELECTRICAL DATA

 

 

 

 

COMPRESSORS

 

COND. FAN

SUPPLY AIR

MIN.

 

 

 

 

 

 

 

 

 

 

 

MOTORS

BLOWER

MAX. TIME

MIN.1 WIRE

 

 

POWER

 

#1

#2

 

CIRCUIT

MODEL

 

 

(#1 & #2)

MOTOR

DELAY FUSE

SUPPLY

 

 

 

 

 

 

AMPACITY

SIZE 75°C

 

 

 

 

 

 

 

 

 

 

 

 

SIZE (AMPS)

 

 

 

RLA

 

LRA

RLA

 

LRA

HP

FLA

HP

FLA

(AMPS)

 

 

 

 

 

 

(ea.)

(ea.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

28.6

274

14.3

 

137

1

4.1/4.2

5

11.8

77.8/77.0

90

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DHG180

 

460-3-60

14.4

 

138

7.2

 

69

1

2.1

5

5.9

42.7

50

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

11.4

 

116

5.7

 

58

1

1.4

5

5.2

30.7

35

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

28.6

274

28.6

 

274

1

4.1/4.2

7.5

18.6

98.6/96.8

110

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DHG240

 

460-3-60

14.4

 

138

14.4

 

138

1

2.1

7.5

9.3

52.2

60

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

11.4

 

116

11.4

 

116

1

1.4

7.5

7.5

40.2

45

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1Although these sizes are based on copper conductors aluminum wire can be used. Refer to the national electric code (in USA) or the current Canadian Electrical Code (in Canada) to determine the proper size.