Energy Tech Laboratories DHG180 Condensate Drain, Recommended Drain Piping, Compressors, Filters

Models: DHG180 DHG240

1 28
Download 28 pages 15.66 Kb
Page 7
Image 7
CONDENSATE DRAIN

035-17233-000-C-0702

CONDENSATE DRAIN

Plumbing must conform to local codes. Use a sealing com- pound on male pipe threads. Install a condensate drain line from the 1" NPT female connection on the unit to an open

drain.

FIGURE 4 : RECOMMENDED DRAIN PIPING

An alternate drain connection (1" NPT female coupling) is provided inboard on the same centerline as the exterior loca- tion.

NOTE: The condensate drain line MUST be trapped to pro- vide proper drainage. See Figure 4.

COMPRESSORS

Units are shipped with compressor mountings factory-

adjusted and ready for operation.

Do Not loosen compressor mounting bolts.

FILTERS

Two-inch filters are supplied with each unit. Filters must always be installed ahead of the evaporator coil and must be kept clean or replaced with same size and type. Dirty filters will reduce the capacity of the unit and will result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in Table 6.

SERVICE ACCESS

Access to all serviceable components are provided by the fol- lowing removable panels:

Compressor compartment

Gas Heat compartment (Two panels)

Side Supply & Return Air compartments (Two panels)

Blower compartment (Three panels)

Main control box

Filter compartment

Outdoor Air compartment (Two panels)

Refer to Figure 10 for location of these access panels.

Make sure that all screws and panel latches are replaced and properly positioned on the unit to maintain an air-tight seal.

THERMOSTAT

The room thermostat should be located on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with thermostat for general installation procedure. Seven color coded insulated wires (#18 AWG) should be used to connect thermostat to unit.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the National Electrical Code, ANSI / NFPA No. 70 (latest edition) and/or local ordinances. The unit must be electrically grounded in accordance with N.E.C. and/or local codes. Volt- age tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 2.

The internal wiring harness furnished with this unit is an inte- gral part of a ETL design certified unit. Field alteration to com- ply with electrical codes should not be required.

A fused disconnect switch should be field provided for the unit. The switch must be separate from all other circuits. Wire entry at knockout openings require conduit fittings to comply with NEC and/or local codes. Refer to Figure 10 for installa- tion location. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram and the same minimum gauge as the replaced wire.

Electrical line must be sized properly to carry the load. Each unit must be wired with a separate branch circuit fed directly

from the meter panel and properly fused.

Refer to Figure 5 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring infor- mation.

Unitary Products

7

Page 7
Image 7
Energy Tech Laboratories DHG180, DHG240 Condensate Drain, Recommended Drain Piping, Compressors, Filters, Service Access