Energy Tech Laboratories EDP70 manual MI00/10056 rev.1--05/2001

Models: EDP70

1 65
Download 65 pages 31.4 Kb
Page 10
Image 10

Reserve Supply

AC Supply

S3

Maintenance By-pass

S2

 

S1

S4

Battery

24/36kVA Ratings

Contactor

S3

Maintenance By-pass

Reserve Supply

S2

S5

 

S1

S4

AC Supply

 

 

 

Battery

50/80kVA Ratings

 

Contactor

480Y/277V

208Y/120V

Figure 5 – Re-establishing the Utility Supply

When the utility supply returns within acceptable limits, the UPS returns automatically to normal operation mode as previously described. The rectifier now starts to recharge the battery. However, until recharge has been completed, any further mains failure will result in reduced standby times.

S3

Reserve Supply

S2

S1

AC Supply

S3

Reserve Supply

S2

S1

AC Supply

Maintenance By-pass

S4

Battery

Contactor 24/36kVA Ratings

 

Maintenance By-pass

 

S5

 

480Y/277V

 

S4

 

208Y/120V

Battery

50/80kVA Ratings

Contactor

Figure 6 – Transferring the Load onto the Reserve Supply

Transfer onto the reserve line is caused by two conditions:

a)inverter stop

b)overload

In both instances the load is transferred onto the reserve without interruption. If the overload is temporary, the system will re-transfer from reserve to inverter as soon as the it ceases. This allows for the initial start-up of loads with high or excessive switch-on currents.

page 10 --MI00/10056 rev.1--05/2001

Page 10
Image 10
Energy Tech Laboratories EDP70 manual MI00/10056 rev.1--05/2001