Energy Tech Laboratories EDP70 manual Computer Interface, 11.1 AS400

Models: EDP70

1 65
Download 65 pages 31.4 Kb
Page 60
Image 60

11.0COMPUTER INTERFACE

11.1AS400

The EDP70 PLUS UPS is fitted with a 9 pin female ‘D’ type socket for direct connection to a IBM AS/400computer or equivalent, see figure 21. This facility can also be used with operating system software of other manufacturers. The function of the pins on the socket are shown below:

Pin

DESCRIPTION

FUNCTION NUMBER

Number

 

 

 

 

 

8

EDP70 PLUS UPS ON

The UPS is supplying the load.

 

 

 

6

RESERVE TO LOAD

The reserve AC supply is supplying the load.

 

 

 

9

UTILITY SUPPLY FAIL

The AC utility supply to the UPS has failed.

 

 

 

7

BATTERY LOW

The battery capacity is at a minimum and the

 

 

inverter will shortly shut down and the load will be

 

 

automatically transferred to the reserve AC supply.

 

 

 

5

COMMON

All the above are connected to common when the

 

 

function is true.

 

 

 

Fig.21: EDP 70 Plus Computer Interface Pin Layout

page 60 --MI00/10056 rev.1--05/2001