Energy Tech Laboratories EDP70 manual Storage, Installation, Mechanical characteristics

Models: EDP70

1 65
Download 65 pages 31.4 Kb
Page 13
Image 13

3.0STORAGE

If the EDP70 PLUS UPS cannot be installed within sixty days of delivery, there is a danger of the integral battery becoming discharged thereby sustaining permanent damage and affecting the standby period available and battery life. The date the battery was last recharged and the date the battery is due for its next recharge are both stamped on the packaging accompanying the unit. If you intend to store the unit, please refer to the recharge date.

When the EDP70 PLUS is due to be recharged, refer to the Installation instructions and connect the EDP70 PLUS UPS to a temporary AC supply. The battery MUST be recharged for at least 24 hours every 3 months.

4.0INSTALLATION

4.1Mechanical characteristics

-

Ambient temperature

 

 

 

18°F[-10°C] to 104°F [+40°C ]

 

- Relative Humidity (w/out condensing @ 68°F[20°C])

< 90%

 

 

- Max altitude (w/out derating)

 

3300 feet [1000 m] above sea-level

 

- Protection degree (panel fitted)

 

 

 

 

 

 

-

Input cables

 

 

 

 

bottom

 

-

Air inlet

 

 

 

 

 

bottom

 

-

Air outlet

 

 

 

 

 

rear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS model

 

 

 

Description

u.m.

 

24

36

 

 

50

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

width

In

 

27.5 [700]

27.5 [700]

 

 

35.4 [900]

35.4 [900]

 

 

 

depth

[mm]

 

28.7 [730]

28.7 [730]

 

 

28.7 [730]

28.7 [730]

 

 

 

height

 

 

56 [1420]

56 [1420]

 

 

63 [1600]

63 [1600]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

w/out cells

Lbs

 

880 [400]

1300 [590]

 

1342 [610]

1800 [818]

 

 

Weight

25 Ah cells

[kg]

 

1342 [610]

n.a.

 

 

n.a.

n.a.

 

 

(UPS +

30 Ah cells

 

 

1456 [662]

n.a.

 

 

 

 

 

 

 

 

n.a.

n.a.

 

 

Battery)

35 Ah cells

 

 

1526 [694]

n.a.

 

 

 

 

 

 

 

 

n.a.

n.a.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Floor Area

In2[m2]

 

789 [0.511]

789 [0.511]

 

1019 [0.657]

1019 [0.657]

 

 

Floor

w/out cells

Lbs/in2

 

1.12 [782]

1.65 [1155]

 

1.32 [930]

1.77 [1245]

 

 

Loading

25 Ah cells

[kg/m2]

 

1.70 [1194]

n.a.

 

 

n.a.

n.a.

 

 

(UPS +

30 Ah cells

 

 

1.85 [1296]

n.a.

 

 

 

 

 

 

 

 

n.a.

n.a.

 

 

Battery)

35 Ah cells

 

 

1.93 [1358]

n.a.

 

 

 

 

 

 

 

 

n.a.

n.a.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air-Flow

cfm

 

235

647

 

 

 

 

 

 

 

 

[mc/h]

 

[400]

[1100]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Acoustic Noise

dBA

 

52

55

 

 

 

 

 

 

100% Linear Load

 

 

 

 

 

 

 

 

Notes:

1)

n.a. = not applicable

 

 

 

 

 

 

2)Longer autonomies, and battery for EDP above 20 kVA are available with external battery cubicles.

MI00/10056 rev.1--05/2001-- page 13

Page 13
Image 13
Energy Tech Laboratories EDP70 manual Storage, Installation, Mechanical characteristics