1.5Operational modes

S3

Maintenance By-pass

S2

 

S1

LOAD

AC Supply

S4

Battery

24/36kVA Ratings

Contactor

S3

Maintenance By-pass

S2

S5

 

480Y/277V

 

LOAD

S1

S4

AC Supply

208Y/120V

 

Battery

 

Contactor

50/80kVA Ratings

Figure 3 – Normal operation

During normal operation the load is supplied by the mains through the rectifier and inverter. The rectifier also supplies the current for recharging and maintaining the battery in a fully charged state.

S3

Maintenance By-pass

Reserve Supply

S2

 

 

 

S1

S4

LOAD

AC Supply

 

 

 

 

 

Battery

 

 

 

Contactor

 

24/36kVA Ratings

S3

Maintenance By-pass

Reserve Supply S2

S5

S1

S4

AC Supply

 

Battery

50/80kVA Ratings

Contactor

480Y/277V

LOAD

208Y/120V

Figure 4 – Utility Supply failure

When the utility supply voltage is absent or outside the allowed tolerances, the battery supplies the inverter. This will be indicated on the UPS front panel display and the Remote Alarm Unit (if fitted). The standby time available depends both on the capacity of the battery and on the size of load. It is possible to extend autonomy by reducing the output power by disconnecting non-important loads. In all cases, the alphanumerical display shows the residual autonomy.

MI00/10056 rev.1--05/2001-- page 9