Hinged panel security screws

Cable support

Cable channel

Figure 17 - 24 – 12/18/24kVA: Switches

Access to the terminals for electrical connections is as follows:

a)Remove front panel see Figure 16.

b)Remove the two securing screws for the hinged front panel.

c)This exposes the electrical terminal rail, see Figure 18

d)Remove the screws securing the access plate.

e)Push the interconnection cables up through the cable channel and the access plate.

f)Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be terminated with the correct size lugs and connected on the bottom side terminals as marked.

g)Install or start-up batteries see section 13.1

h)Replace and tighten the terminal securing screws fully clockwise and refit the access plate.

i)Replace the terminal board compartment panel and the front cover.

OBSERVE POLARITIES AND ORIENTATIONS.

See Remote Alarms and Computer Interface for connections to these facilities. For optional battery cubicles, refer to section 13.2.