Initial Installation
VENT PARTS:
Table 2: Vent part numbers.
Simpson Duravent (SD), Selkirk (SEL), and Security Chimneys (SC), must state if galvanized or black wanted, PART NUMBERS:
SD | SEL | SC | Description | SD | SEL | SC | Description |
|
|
|
|
|
|
|
|
908 | SV4L6 | 6” pipe length | 911 |
|
| 11” to 14 5/8” pipe, adjustable | |
907 |
| 9” pipe length |
|
| 4” to 10” pipe , adjustable | ||
|
|
|
|
|
|
|
|
906 | SV4L12 | 12” pipe length |
|
| SV4LA12 | 11⁄2” to 12” pipe , adjustable | |
|
|
|
|
|
|
|
|
904 | SV4L24 | 24” pipe length | 943 |
| Flashing, 0/12 to 6/12 roof pitch | ||
|
|
|
|
|
|
|
|
903 | SV4L36 | 36” pipe length | 943S |
| Flashing, 7/12 to 12/12 roof pitch | ||
|
|
|
|
|
|
|
|
902 | SV4L48 | 48” pipe length |
|
| SV4FA | Flashing, 1/12 to 7/12 roof pitch | |
|
|
|
|
|
|
|
|
945 | SV4EBR45 | 45° elbow, black |
|
| SV4FB | Flashing, 8/12 to 12/12 roof pitch | |
|
|
|
|
|
|
|
|
990 | SV4EBR90 | 90° elbow, black | 943F |
| SV4F | Flat flashing | |
|
|
|
|
|
|
|
|
950 | SV4VS | Vinyl siding standoff/sheild | 980 | SV4CGV | Vertical termination | ||
|
|
|
|
|
|
|
|
942 | SV4RSN | Wall thimble | 991 |
| High wind vertical termination | ||
|
|
|
|
|
|
|
|
941 | SV4CSB | Cathedral Support Box | 984 | SV4CHC | Horizontal square termination | ||
|
|
|
|
|
|
|
|
981 | SV4STC36 | 36” Snorkel Termination | 985 |
| High wind horizontal termination | ||
|
|
|
|
|
|
|
|
953 | SV4FC | Storm collar | 978 | SV0FAK | Vertical termination kit | ||
|
|
|
|
|
|
|
|
963 | SV4BF | Fire stop | 970 | SV0SHK | Horizontal termination kit | ||
|
|
|
|
|
|
| SD: Basic Kit, SEL: Kit A, SC: Standard Kit |
988 | SV4BM | Wall strap/support/band |
|
|
| ||
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| 971 | SV0SHK2 | Horizontal termination kit | |
|
|
|
|
|
|
| SD: Kit A, SEL: Kit B, SC: Kit |
|
|
|
|
|
|
|
|
This fireplace have been tested and certified for use with SIMPSON DURAVENT TYPE GS PIPE FOR GAS STOVES. SELKIRK
When planning your installation, it will be necessary to select the proper length of vent pipe for your particular requirements. It is important to note when passing through a wall, the maximum allowable wall thickness is 10 inches (254 mm), 11⁄2” inches clearance to combustibles must be maintained.
A MINIMUM VERTICAL LENGTH OF 24” (610 mm) TO THE FIRST 90° ELBOW IS REQUIRED. WITH THIS MINIMUM VERTICAL RISE, HORIZONTAL RUNS OF FROM 1 FT (305 mm) to 3 FT (915 mm)
ARE PERMITTED TO REACH THE OUTSIDE VENT TERMINATION.
BEFORE BEGINNING THE INSTALLATION TAKE CARE TO ENSURE AN APPROPRIATE OUTSIDE LOCATION FOR THE VENT TERMINATION CAN BE ACCOMMODATED. FOLLOW THE VENT LENGTH DIAGRAM
PRECISELY.
VENTING TERMINALS CANNOT BE RECESSED INTO A WALL OR SIDING.
If extra elbows are being used, overall allowable length will be reduced by 3 ft (915 mm) per additional elbow.
11