2.0.UPS Output Requirements
IMPORTANT
Note: The outputs of SG 5 & 6kVA models are not configured for 208 or 240Vac
MODEL | OUTPUT REQUIREMENTS | RECOMMENDED OUTPUT |
| ||
|
| CIRCUIT BREAKER |
|
| |
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire | 30A | |
Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) | 50A | |
|
| |
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire | 30A | |
Output 2: None |
|
|
|
|
|
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire | 30A | |
Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) | 50A | |
|
|
|
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire | 30A | |
Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) | 50A | |
|
| |
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire | 30A | |
Output 2: None |
|
|
|
|
|
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire | 30A | |
Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) | 50A |
Terminal Designation Numbers 1 2 3 4 5 6 7 8 9 10
View of the Input/Output Hardwire Terminal Block
This terminal block is located on the UPS rear panel and shown with the conduit mounting and
access cover plates removed.
Use only the lower terminals and wire securing screws when making wiring connections to
the UPS.
DO NOT USE THE UPPER TERMINAL CONNECTIONS
Refer to the Wire Gauge Table on Page 7 for recommended wire sizes.
Refer to the Torque Specification Table on Page 7 and tighten all 20 screws as specified. Refer to Pages
8