DRY CONTACT & OPTO COUPLER INTERFACE BOARD OPTIONS
Typical Falcon Dry Contact Relay Board
JP1 | J1 |
JP2 | J2 |
JP3 | J3 |
PIN & JUMPER ASSIGNMENT FOR THE FALCON
UA88374 RELAY OPTION BOARD
(no on-bypass signal)
PIN | DESCRIPTION |
1Low Battery ( When UPS reaches low battery, contact activates) (J1,
2JP2 shorted = Low Battery common & all other shorted JP commons JP2 open = common for low battery only
3Utility Loss N.O. ( At loss of utility voltage, contact activates)
4Utility Loss N.C. ( At loss of utility voltage, contact activates)
5JP1 shorted = Utility Loss common & all other shorted JP commons JP1 open = Utility Loss common only
6Remote Shutdown common
7Remote Shutdown
(J2,
8Alarm (Upon a UPS fault or failure the contact activates) (J3,
9JP3 shorted = Alarm common & all other shorted JP commons JP3 open = Alarm common only
| PIN & JUMPER ASSIGNMENT FOR THE FALCON |
| UA88376 RELAY OPTION BOARD |
| (with |
|
|
| |
PIN | DESCRIPTION |
1Low Battery ( When UPS reaches low battery, contact activates) (J1,
2JP2 shorted = Low Battery common & all other shorted JP commons JP2 open = common for low battery only
3Utility Loss N.O. ( At loss of utility voltage, contact activates)
4Utility Loss N.C. ( At loss of utility voltage, contact activates)
5JP1 shorted = Utility Loss common & all other shorted JP commons JP1 open = Utility Loss common only
6Remote Shutdown common
7Remote Shutdown
(J2,
8On Bypass or Alarm (Upon the UPS going to bypass or a UPS failure the contact activates)
(J3,
9JP3 shorted = On bypass, Alarm common & all other shorted JP commons
JP3 open = On bypass, Alarm common only