Installation Instructions For Hardwire Models (see model numbers referenced below)

1.0UPS Input & Output Requirements.

IMPORTANT

Note: All SG Series hardwire UPS models must be installed by a licensed electrician, in accordance with the National Electrical Code (NEC) ANSI/NFPA70 and all local regulations. It is further required that the input of SG Series hardwire UPS be wired to a building service panel incorporating a dedicated “branch rated” circuit breaker of the proper rating.

 

 

 

INPUT REQUIREMENTS

 

 

 

MODEL

 

 

REQUIRED INPUT

 

 

 

 

 

 

CIRCUIT BREAKER

SG5K-1TX:- 120Vac, 50/50Hz, 38.7A, 1 phase, 3 wire

 

50A

SG5K-2T - 208-240Vac, 50/60Hz, 19.5A, 1 phase, 3 wire

 

30A

SG5K-2TX - 208-240Vac, 50/60Hz, 20.3A, 1 phase, 3 wire

30A

SG6K-1TX - 120Vac, 50/60Hz, 46.6A, 1 phase, 3 wire

 

70A

SG6K-2T - 208-240Vac, 50/60Hz, 23.4A, 1 phase, 3 wire

 

30A

SG6K-2TX - 208-240Vac, 50/60Hz, 24.3A, 1 phase, 3 wire

30A

 

 

 

 

 

 

 

 

 

 

 

WIRE GAUGE CHART

 

 

 

 

MODEL

AC INPUT

AC OUTPUT(S)

EXTERNAL

 

 

 

-1 = 120 Vac

120 Vac

208-240 Vac

BATTERY

 

 

 

-2 = 208-240 Vac

 

 

 

240 dc

 

 

 

 

 

 

 

 

 

SG5K-1TX

8 Awg. 600V

10 Awg. 600V

 

12 Awg. 600V

10 Awg. 600V

 

 

 

75°C CU

75°C CU

 

75°C CU

75°C CU

 

 

SG5K-2T

12 Awg. 600V

N/A

 

12 Awg. 600V

10 Awg. 600V

 

 

 

75°C CU

 

75°C CU

75°C CU

 

 

 

 

 

 

 

SG5K-2TX

12 Awg. 600V 75°C

10 Awg. 600V

 

12 Awg. 600V

10 Awg. 600V

 

 

 

CU

75°C CU

 

75°C CU

75°C CU

 

 

SG6K-1TX

6 Awg. 600V

8 Awg. 600V

 

10 Awg. 600V

10 Awg. 600V

 

 

 

75°C CU

75°C CU

 

75°C CU

75°C CU

 

 

SG6K-2T

10 Awg. 600V

N/A

 

10 Awg. 600V

10 Awg. 600V

 

 

 

75°C CU

 

75°C CU

75°C CU

 

 

 

 

 

 

 

SG6K-2TX

10 Awg. 600V 75°C

8 Awg. 600V

 

10 Awg. 600V

10 Awg. 600V

 

 

 

CU

75°C CU

 

75°C CU

75°C CU

 

 

External Battery &

16 Awg, 600V

N/A

 

N/A

10 Awg. 600V

 

 

Charger System

75°C CU

 

75°C CU

 

 

 

 

 

ONLY USE WIRE WITH SOLID COPPER CONDUCTORS FOR ALL INPUT/OUTPUT/BATTERY WIRING

SCREW TORQUE SPECIFICATIONS FOR

INPUT/OUTPUT WIRING BLOCK

UPS & BATTERY BANK

 

 

Wire Gauge

Torque

 

 

 

(inch pounds)

 

 

18 - 10 Awg.

20

 

 

8-6 Awg

25 - 30

CAUTION

To reduce the risk of fire, connect only to a circuit providing over-current protection incorporating the specified "branch rated" over-current protection device in accordance with the National Electrical Code, ANSI/NFPA 70.

7

Page 9