3.Select a suitable location for the the extended battery bank, preferably close to the UPS to minimize the risk of DC voltage drop due to excessive long wiring runs. Use 10 Awg, 600V insulated wire for all hardwired DC connections between the UPS and battery bank(s). See Wire Guage Chart of page 7.
VERIFY THE FLOOR OR SURFACE SUPPORTING THE UPS WILL SUPPORT THE WEIGHT OF THE UPS AND ANY OPTIONAL EXTENDED BATTERY BANKS.
FLOOR STANDING EXTENDED BATTERY BANKS = 363 lbs. (165 kg) MAX. (EACH BANK)
4.Remove the lower wiring access cover plate located on the rear panel of the battery bank.
5.Remove the
6.Install all of the required wiring. Reference the tables on page 7 for wire Gauge and terminal block torque specifications.
7.Verify all wiring connection to the battery bank(s), UPS and utility sources prior to ` turning on any circuit beakers or equipment power switches.
8.ALWAYS TURN ON THE BATTERY BANK DC DISCONNECT(S) AND THE UPS BATTERY CIRCUIT BREAKER PRIOR TO SWITCHING ON THE UPS AC INPUT CIRCUIT BREAKER.
EXTENDED BATTERY BANK SELECTION GUIDE
(Please specify a hardwire configuration at the time of order)
| BATTERY OPTION |
|
|
|
|
| |
| MODELS | ||||||
| W/O Charger |
|
|
|
|
| |
| BATTERIES | 40 Pieces 12V, | 80 Pieces 12V, 7AH | 60 Pieces 12V, | 80 Pieces 12V, 7AH | 160 Pieces 12V, | |
| 7AH |
| 7AH |
| 7AH | ||
|
|
|
|
| |||
| BATTERIES IN UPS |
|
| 20 each of 12V, 7AH |
|
| |
| # of CASES | 1 Floor Standing | 2 Floor Standing | 3 Floor Standing | 4 Floor Standing | 8 Floor Standing | |
| Inches | 32.1 x 10.2 x 21.8 | 32.1 x 10.2 x 21.8 | 32.1 x 10.2 x 21.8 | 32.1 x 10.2 x 21.8 | 32.1 x 10.2 x 21.8 | |
| (mm) | (814 x 259 x 554) | (814 x 259 x 554) | (814 x 259 x 554)) | (814 x 259 x 554) | (814 x 259 x 554) | |
| RUN TIME @ 1000W | 190 Min. | 340 Min. | 500 Min. | 820 Min. | 1400 Min. | |
| RUN TIME @ 1750W | 92 Min. | 180 Min. | 265 Min. | 450 Min. | 740 Min. | |
| RUN TIME @ 2500W | 60Min. | 112 Min. | 180 Min. | 305 Min. | 505 Min. | |
| RUN TIME @ 3500W | 37.5 Min. | 78 Min. | 120 Min. | 210 Min. | 340 Min. | |
| 5kVA Full Load | ||||||
|
|
|
|
|
| ||
| RUN TIME @ 4200W | 29 Min. | 60 Min. | 92 Min. | 165 Min. | 270 Min. | |
| 6kVA Full Load | ||||||
|
|
|
|
|
| ||
|
|
|
| CHARGER OPTION INFORMATION |
|
| |
| BATTERY OPTION |
|
|
|
|
|
|
| MODELS |
| SGB2S7 | ||||
| With 120Vac Charger |
|
|
|
|
|
|
| BATTERY OPTION |
|
|
|
|
|
|
| MODELS |
| SGB2S7 | ||||
| With |
| |||||
|
|
|
|
|
|
| |
| Charger |
|
|
|
|
|
|
| CHARGER OUTPUT | 275Vdc @ 1.3A | 275Vdc @ 1.3A | 275Vdc @ 1.3A | 275Vdc @ 1.3A | 275Vdc @ 1.3A | |
| # OF CHARGERS | 1 | 2 | 3 | 4 | 8 | |
|
|
| |||||
|
|
|
|
|
|
|
|
Battery run times are for reference only and may vary due to application, environment and the condition of the batteries.
11