Falcon SG6K-2TC, SG5K-1TXC, SG5K-2TXC Installation Instructions, General Common for all models

Models: SG5K-2TC SG6K-1TX SG5K-2TXC SG5K-2TX SG5K-1TX SG6K-2TC SG5K-2T SG6K-2T SG5K-1TXC

1 30
Download 30 pages 47.76 Kb
Page 6
Image 6

CHAPTER 2

INSTALLATION INSTRUCTIONS

General - Common for all models

1.Verify the following is included in the UPS shipping carton:

(1) UPS, (1) Software Diskette(s) & Manual, (1) Owners Manual & (1) UPS/Computer Cable.

2.Verify the UPS unit is configured for the proper input/output voltage and frequency. This information is stated on the nameplate label located on the rear or the side panel of the unit. If any special input plug and output receptacle configurations were specified at the time of order, verify for proper configuration.

3.Set the output voltage and green mode switches located on the UPS rear panel for the nominal UPS output voltage desired. See the switch setting tables located on page 5.

In most cases the nominal UPS output voltage should be set to match the incoming utility voltage. This will assure a close matching voltage in the event the UPS is placed on bypass. NOTE: Disregard the "ON" marking on the side of the actual dip switch housing; use the tables in this manual or the silkscreen on the UPS rear panel only.

Dip switch 3 "enables" or "disables” the "Green Mode" function. The UPS is shipped from the factory with the switch set in the "disabled" position (up). If SW3 is switched down or to the "enabled" position, the Green Mode function is activated. When the

load connected to the output of the UPS drops to under 10% of the full rated UPS output for 30 seconds, the UPS is automatically placed into bypass and the inverter is turned off.

NO BATTERY BACKUP IS PROVIDED AFTER THE GREEN MODE HAS ACTIVATED.

Dip switch settings must be made while the UPS is turned off. Any changes made while the UPS is turned on will not take effect until the UPS is turn off and back on again since the switch settings are read by the microprocessor only during initial UPS power up.

4.To prevent accelerated battery discharge during shipment, this UPS was shipped with the battery circuit breaker turned off. TURN THE BATTERY DISCONNECT CIRCUIT BREAKER ON PRIOR TO TURNING ON THE UPS INPUT CIRCUIT BREAKER.

CAUTION

NEVER TURN THE BATTERY CIRCUIT BREAKER OFF WHILE THE UPS AC CIRCUIT BREAKER IS TURNED ON AND OPERATING FROM THE UTILITY VOLTAGE, OR UPS DAMAGE MAY RESULT. UPS MUST BE COMPLETELY SHUT DOWN PRIOR TO DISABLING THE INTERNAL BATTERY SUPPLY.

CAUTION

In the event this UPS is to be turned off or stored for more than two weeks, the battery circuit breaker must be turned to the off position to prevent battery discharge. If placed in long-term storage, every four months the UPS must be plugged in and turned on for 24 hours to allow the batteries to recharge and prevent battery damage. Failure to follow these procedures will invalidate your warranty.

4

Page 6
Image 6
Falcon SG6K-2TC, SG5K-1TXC, SG5K-2TXC, SG5K-2TC, SG6K-1TX Installation Instructions, General Common for all models