Falcon SG6K-2TC, SG5K-1TXC, SG5K-2TXC, SG5K-2TC Refer to page 20 for Operating Instructions

Models: SG5K-2TC SG6K-1TX SG5K-2TXC SG5K-2TX SG5K-1TX SG6K-2TC SG5K-2T SG6K-2T SG5K-1TXC

1 30
Download 30 pages 47.76 Kb
Page 17
Image 17

Typical SG5 & 6kVA Rear Panel Layout (Shown with Power Distribution Center )

Output Voltage & Green Mode

Select Switches

RS-232 Computer Interface

Connector

COOLING FANS

DO NOT BLOCK AIR FLOW

INPUT AC CIRCUIT BREAKER

ALWAYS TURN ON AFTER THE

BATTERY CIRCUIT BREAKER

HAS BEEN TURNED ON

OUTPUT POWER DISTRIBUTION

CENTER (see page 14)

Communications Option Slot

Cover Plate

MAINTENANCE BYPASS

SWITCH

REFER TO PAGE 20 FOR

OPERATING INSTRUCTIONS

WARNING

NEVER TURN THIS SWITCH TO

THE ON POSITION UNLESS THE

UPS HAS BEEN PLACED INTO

MANUAL BYPASS, OR THE UPS

HAS BEEN TURNED OFF

BATTERY CIRCUIT BREAKER &

DISCONNECT

VERIFY THIS DISCONNECT IS IN

THE OFF POSITION WHEN:

*The UPS is being installed.

*The UPS is to be turned off or stored for more than five days.

*Connecting external battery banks.

*Servicing the UPS.

WARNING

NEVER TURN OFF THIS

DISCONNECT WHILE THE UPS IS

OPERATING FROM UTILITY.

POWER OR DAMAGE MAY RESULT. ALWAYS TURN OFF THE UPS FIRST.

IMPORTANT

TO TURN OFF THE UPS

SWITCH THE INPUT CIRCUIT BREAKER LOCATED ON THE UPS REAR PANEL TO THE “OFF” POSITION AND PRESS THE ON/OFF BUTTON LOCATED ON THE UPS FRONT PANEL UNTIL THE UPS BEEPS. THE UPS WILL RUN FOR ABOUT 30 SECONDS AND SHUT DOWN. DO NOT PRESS THE ON/OFF BUTTON OR TURN THE CIRCUIT BREAKER ON AGAIN DURING THE SHUTDOWN PROCESS OR THE UPS WILL GO TO AN ALARM CONDITION, WARNING THAT THE UPS WAS NOT SHUT DOWN PROPERLY. SHOULD THIS OCCUR, TURN OFF THE INPUT CIRCUIT BREAKER AGAIN AND WAIT UNTIL THE UPS SHUTS DOWN.

15

Page 17
Image 17
Falcon SG6K-2TC, SG5K-1TXC, SG5K-2TXC, SG5K-2TC, SG6K-1TX specifications Refer to page 20 for Operating Instructions