Typical SG5 & 6kVA Rear Panel Layout (Shown with Power Distribution Center )
Output Voltage & Green Mode
Select Switches
Connector
COOLING FANS
DO NOT BLOCK AIR FLOW
INPUT AC CIRCUIT BREAKER
ALWAYS TURN ON AFTER THE
BATTERY CIRCUIT BREAKER
HAS BEEN TURNED ON
OUTPUT POWER DISTRIBUTION
CENTER (see page 14)
Communications Option Slot
Cover Plate
MAINTENANCE BYPASS
SWITCH
REFER TO PAGE 20 FOR
OPERATING INSTRUCTIONS
WARNING
NEVER TURN THIS SWITCH TO
THE ON POSITION UNLESS THE
UPS HAS BEEN PLACED INTO
MANUAL BYPASS, OR THE UPS
HAS BEEN TURNED OFF
BATTERY CIRCUIT BREAKER &
DISCONNECT
VERIFY THIS DISCONNECT IS IN
THE OFF POSITION WHEN:
*The UPS is being installed.
*The UPS is to be turned off or stored for more than five days.
*Connecting external battery banks.
*Servicing the UPS.
WARNING
NEVER TURN OFF THIS
DISCONNECT WHILE THE UPS IS
OPERATING FROM UTILITY.
POWER OR DAMAGE MAY RESULT. ALWAYS TURN OFF THE UPS FIRST.
IMPORTANT
TO TURN OFF THE UPS
SWITCH THE INPUT CIRCUIT BREAKER LOCATED ON THE UPS REAR PANEL TO THE “OFF” POSITION AND PRESS THE ON/OFF BUTTON LOCATED ON THE UPS FRONT PANEL UNTIL THE UPS BEEPS. THE UPS WILL RUN FOR ABOUT 30 SECONDS AND SHUT DOWN. DO NOT PRESS THE ON/OFF BUTTON OR TURN THE CIRCUIT BREAKER ON AGAIN DURING THE SHUTDOWN PROCESS OR THE UPS WILL GO TO AN ALARM CONDITION, WARNING THAT THE UPS WAS NOT SHUT DOWN PROPERLY. SHOULD THIS OCCUR, TURN OFF THE INPUT CIRCUIT BREAKER AGAIN AND WAIT UNTIL THE UPS SHUTS DOWN.
15