FS-8700-31 Siemens TIWAY I

Page 11 of 23

The above map descriptor will continuously write data of type “Loop_Gain” to 2 PLC data memory addresses of 5 and 9. The data to write will be collected from the data array “FLOAT_Data” from offsets 0 and 1.

4.4.5.3.Writing the same value to a block of contiguous PLC data memory locations

Map_Descriptor_Name,

Data_Array_Name, Data_Array_Offset,

Function,

Node_name,

TIWAY_Data_Type,

Address,

Length,

C18_FLOAT_PLC254,

FLOAT_Data,

10,

WRBC,

PLC_254,

Loop_Reset,

0,

3,

TIWAY_Fill_Block_Value, Scan_Interval

 

 

 

 

 

 

50.5,

0s

 

 

 

 

 

 

The above map descriptor will continuously write a value of 50.5 of type “Loop_Reset” to 3 contiguous PLC data memory addresses starting from 0.

4.4.5.4.Writing Drum_Count_Preset data to contiguous PLC data memory locations

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

TIWAY_Data_Type, Address,

Length,

C08_RAW16_PLC01,

RAW16_Data,

70,

WRBC,

PLC_01,

Drum_Count_Preset, 0,

5,

Preset_Step_List,

Scan_Interval

 

 

 

 

 

5 8 9 33 49,

0s

 

 

 

 

 

 

The above map descriptor will continuously write data of type “Drum_Count_Preset” to 5 PLC data memory addresses. The data to write will be collected from the data array “RAW16_Data” from an offset of 70. The Preset Steps associated with the addresses are (address 0):5, (address 1):8, (address 2):9, (address 3):33, and (address 4):49.

4.4.5.5.Writing Drum_Count_Preset data to random PLC data memory locations

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

TIWAY_Data_Type, TIWAY_Address_List,

C08_RAW16_PLC01,

RAW16_Data,

70,

WRBC,

PLC_01,

Drum_Count_Preset, 5 9,

Length, Preset_Step_List, Scan_Interval

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 14
Image 14
FieldServer FS-8700-31 instruction manual C18FLOATPLC254