 | Page 8 of 23  | 
4.4.4.Reading TIWAY data map descriptor examples
4.4.4.1.Reading data from contiguous PLC data memory locations
Map_Descriptor_Name,  | Data_Array_Name,  | Data_Array_Offset,  | Function,  | Node_name,  | TIWAY_Data_Type,  | Address,  | Length,  | 
C01_RAW16_PLC01,  | RAW16_Data,  | 0,  | RDBC,  | PLC_01,  | IE_Ladder,  | 0,  | 10,  | 
Scan_Interval  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
0s  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
The above map descriptor will continuously read 10 data elements starting from address 0 of type “IE_Ladder” from PLC_01. The data will be stored in the data array called “RAW16_Data” from an offset of 0.
4.4.4.2.Reading data from random PLC data memory locations
Map_Descriptor_Name,  | Data_Array_Name,  | Data_Array_Offset,  | Function,  | Node_name,  | TIWAY_Data_Type,  | TIWAY_Address_List,  | Length,  | 
C02_RAW16_PLC01,  | RAW16_Data,  | 10,  | RDBC,  | PLC_01,  | Variable,  | 5 9,  | 2,  | 
Scan_Interval  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
0s  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
The above map descriptor will continuously read 2 data elements from address 5 and 9 of type “Variable” from PLC_01. The data will be stored in the data array called “RAW16_Data” from an offset of 10. The data will be stored at offsets 10 and 11.
4.4.4.3.Reading Drum_Count_Preset data from contiguous PLC data memory locations
Map_Descriptor_Name,  | Data_Array_Name,  | Data_Array_Offset,  | Function,  | Node_name,  | TIWAY_Data_Type, Address,  | Length,  | 
C08_RAW16_PLC01,  | RAW16_Data,  | 70,  | RDBC,  | PLC_01,  | Drum_Count_Preset, 0,  | 5,  | 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408)