FS-8700-31 Siemens TIWAY I

Page 5 of 23

Example

//Client Side Connections

Connections

Port,

 

Protocol,

 

Baud,

 

Parity,

 

Handshaking,

 

Poll_Delay

 

P1,

 

TIWAY_BDLC,

 

9600,

 

None,

 

None,

 

0.100s

 

4.3.Client Side Node Descriptors

 

Section Title

 

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

 

Column Title

 

 

Function

 

 

Legal Values

 

 

Node_Name

 

Provide name for node

 

 

Up to 32 alphanumeric

 

 

 

 

 

characters

 

 

 

 

 

 

 

 

 

 

Node_ID

 

 

Secondary PLC station address to

 

1-254

 

 

 

 

communicate with

 

 

 

 

 

 

 

 

 

 

 

Protocol

 

Specify protocol used

 

TIWAY, TIWAY_BDLC

 

 

Connection

 

 

Specify which port the device is

 

 

P1-P8

 

 

 

 

connected to the FieldServer

 

 

 

 

 

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

//Client Side Nodes

 

Nodes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Node_Name,

 

 

Node_ID,

 

Protocol,

 

Port

 

 

PLC_01,

 

 

01,

 

TIWAY_BDLC,

 

P1

 

4.4.Client Side Map Descriptors

4.4.1.FieldServer Related Map Descriptor Parameters

 

Section Title

 

 

 

 

 

 

 

 

Map Descriptors

 

 

 

 

 

 

 

 

Column Title

 

 

Function

 

 

Legal Values

 

 

Map_Descriptor_Name

 

 

Name of this Map

 

 

Up to 32 alphanumeric

 

 

 

 

Descriptor

 

 

characters

 

 

 

 

 

 

 

 

 

 

 

 

Name of Data Array

 

 

One of the Data Array names

 

 

Data_Array_Name

 

 

where data is to be stored

 

 

from “Data Array” section

 

 

 

 

 

in the FieldServer

 

 

above

 

 

Data_Array_Offset

 

 

Starting location in Data

 

 

0 to maximum specified in

 

 

 

 

Array

 

 

“Data Array” section above

 

 

 

 

 

 

 

 

 

Function

 

 

Function of Client Map

 

 

RDBC, WRBC, WRBX, AWT

 

 

 

 

Descriptor

 

 

 

 

 

 

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 8
Image 8
FieldServer instruction manual Client Side Node Descriptors, FS-8700-31 Siemens Tiway Example